Mitsubishi LJ61BT11 User Manual page 43

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

compatible
remote
output RY
compatible
remote
output RY
3 - 16
2 A link is performed as shown in the following areas.
Master station
(Station number 1:
Occupies 1 station)
additional mode
Ver. 1
Station number 1
to
Ver. 2
Station number 2
Station number 3
Station number 4
Station number 5
Station number 6
Station number 7
to
3 The remote net ver.2 mode and remote net additional mode cannot be used with
the QJ61BT11.
4 Data link is not available when the version set in the station type of the master
station information is different from that of the remote station.
For example, when the station type of the master station information is set as
"Ver.1 remote device station" although the actual remote device station is set to
"Ver.2 remote device station", data link cannot be performed with the "ERR." LED
on the master station flashing and the "L RUN" LED on the remote device station
turned OFF.
Local station
Local station
Ver. 1 mode
Ver. 2 mode
(Station number 2:
Occupies 1 station)
Station number 1
Station number 2
Station number 3
Station number 4
Station number 5
Station number 6
Station number 7
to
Station number 1
Station number 2
Station number 3
Station number 4
Station number 5
Station number 6
Station number 7
to
double
3 SPECIFICATIONS
Local station
Standby master station
additional mode
additional mode
(Station number 3:
(Station number 7:
Occupies 4 stations)
Occupies 1 station)
Remote input RX
Station number 1
Station number 1
to
Station number 2
Station number 2
Station number 3
Station number 3
Station number 4
Station number 4
Station number 5
Station number 5
Station number 6
Station number 6
Station number 7
Station number 7
to
double
to
to
octuple
3 - 16

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L26cpu-bt

Table of Contents