Mitsubishi LJ61BT11 User Manual page 348

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

Error code
Error details
(hexadecimal)
Standby master station
B39A
specification error (loading
status)
B39B
Reserved station setting error
Standby master station setting
B39C
error
Reserved station 0 points
B39D
setting error
8/16-point remote I/O station
B39E
setting error
Remote net additional mode
B39F
station number invalid
Mode invalid (between master
B3A0
and local/standby master
stations)
B3A1
Standby master setting invalid
Remote I/O net mode station
B3A2
type invalid
B3A3
Assignment error
B3A4
Parameter mismatch
15 - 27
Cause of error occurrence (details)
The station number of the standby
master station differs from that set in the
"Standby Master Station No." network
parameter of the master station, or the
station set in the "Standby Master Station
No." network parameter of the master
station is a local station.
All stations were set as reserved stations.
Any other than Intelligent device station
has been set to the station type for the
"Standby Master Station No." specified in
the master station network parameter.
The mode setting is different between the
master and standby master stations.
Reserved station 0 points setting has
been made in the remote net additional
mode.
Reserved station 0 points setting has
been made for the station that is not a
reserved station.
Remote I/O station points setting is 8/16
points in the remote net additional mode.
8/16 points setting has been made for the
station other than the remote I/O station.
Make 8/16 points setting for the same
remote I/O station.
In the remote net additional mode, the
"maximum station number of ver.1
compatible slave stations" is greater than
the "minimum station number of ver.2
compatible slave stations" in the network
parameter setting.
Model invalid has occurred between the
master and local/standby master
stations.
• The mode differs between the master
and standby master stations.
• The local station is set to the remote
net additional mode, and the master
station is set to other than the remote
net additional mode.
• The local station is in the remote net
ver.2 mode or remote net additional
mode, and the master station is in the
remote net ver.1 mode.
At the time of parameter setting with
dedicated instruction, an invalid value
has been set to switch 5 of the intelligent
function module switch setting.
At the time of parameter setting with
dedicated instruction, the station type of
other than the remote I/O station has
been set in the remote I/O net mode.
In the remote net Ver.2 mode or remote
net additional mode, total points for
remote stations set in the station
information have exceeded the maximum
of 8192.
When the standby master station was
operating as the master station with the
master station duplex function, the
network parameter setting of the faulty
master station was changed.
Corrective action
Change the parameter setting
of the master station, or change
the station number setting of
the local/standby master
station, and then reset the
programmable controller CPU
of the local/standby master
station.
Check the reserved station
settings.
Specify the standby master
station as an intelligent device
station.
Make the same setting to the
master and standby master
stations.
Change the mode to the remote
net ver.2 mode.
Set the station of reserved 0
points setting as a reserved
station.
Change the mode to the remote
net ver.2 mode.
8 points setting and 16 points
setting have been made for the
same remote I/O station.
Make either 8 points setting or
16 points setting for the remote
I/O station.
In the remote net additional
mode, make network parameter
setting so that the "maximum
station number of ver.1
compatible slave stations" is
less than the "minimum station
number of ver.2 compatible
slave stations".
After correcting the mismatch of
modes between the master and
local/standby master stations,
reset the programmable
controller CPU.
Set a correct value to switch 5
of the intelligent function
module switch setting.
Set all station types to the
remote I/O station.
Check the points for remote
stations in the station
information setting.
Return the network parameter
setting of the master station to
the original value.
15 TROUBLESHOOTING
Detectability
Master station
Local station
(To the next page)
15 - 27