Mitsubishi LJ61BT11 User Manual page 242

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

11 EXAMPLE OF COMMUNICATION BETWEEN THE MASTER STATION AND REMOTE DEVICE STATIONS
(4) Remote device station initial setting
11 - 5
(a) Setting the target station number
Set the target station for which the initial setting is performed.
1) Setting the target station number
Set the target station No. to "1".
2) Selecting the Regist Procedure
Click the "Regist Procedure" of the target station number "1".
(b) Setting the regist procedure registration
Set the conditions and details of the remote device station settings.
For more detailed information about the settings, refer to the User's Manual
for the remote device station.
In this section, AJ65VBTCU-68ADVN is used as an example for the Regist
procedure registration.
The details to be set are as follows:
Set channels 1 and 2 to A-D conversion enable (the first condition).
Set the Input range of channel 1 to 0 - 5V, and channel 2 to User range
setting 1 (the second condition).
Set channel 1 to Sampling processing, and specify channel 2 as Average
processing and set it to Number of times (the third condition).
Set channel 2 Average number of times to 16 times (the forth condition).
Turn the Initial data processing completed flag to ON (the fifth condition).
Turn the Initial data setting request flag to ON (the sixth condition).
Turn the Initial data processing completed flag to OFF (the seventh
condition).
Turn the Initial data setting request flag to OFF (the eighth condition).
11 - 5