Mitsubishi LJ61BT11 User Manual page 112

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

Programmable
controller CPU
6)
W
[Remote register RWw when the AJ65BT-64AD is set to station number 1]
Address
RWw0
RWw1
RWw2
RWw3
RWw4
RWw5
RWw6
RWw7
The data to be written to the remote registers RWw0 to RWwn is predefined for each remote device station.
8 - 6
[Writing to the remote register RWw]
6) The transmission data of the CPU device set with the automatic refresh
parameters is stored in the "remote register RWw" buffer memory.
7) The data stored in the "remote register RWw" buffer memory is
automatically sent to the remote register RWw of each remote device
station.
Master station
Remote register RWw
RWw0
RWw1
RWw2
RWw3
RWw4
RWw5
RWw6
RWw7
RWw8
RWw9
RWwA
RWwB
RWwC
RWwD
RWwE
RWwF
RWw10
to
RWwFF
Signal direction: master module
A-D conversion enable/disable setting
Remote device station
(Station number 1:
occupies 2 stations)
Remote register RWw
Numeric data for
averaging processing
setting, A-D conversion
enable/disable setting,
etc.
RWw0
RWw1
RWw2
7)
RWw3
RWw4
RWw5
RWw6
RWw7
7)
AJ65BT-64AD
Description
Averaging process setting
CH1 average time, number of times
CH2 average time, number of times
CH3 average time, number of times
CH4 average time, number of times
Data format
Not used
8 FUNCTIONS
Remote device station
(Station number 3:
occupies 2 stations)
Remote register RWw
Numeric data for
averaging processing
setting, A-D conversion
enable/disable setting,
etc.
RWw0
RWw1
RWw2
RWw3
RWw4
RWw5
RWw6
RWw7
8 - 6