Mitsubishi LJ61BT11 User Manual page 387

Melsec l series cc-link system master/local module
Table of Contents

Advertisement

Number
Name
SB0008
Loop test request
(5E0
, b8)
H
SB0009
Parameter information
(5E0
, b9)
read request
H
SB000B
Transmission speed
(5E0
, b11)
test request
H
SB000C
Forced master
(5E0
, b12)
switching
H
Remote device station
SB000D
initialization procedure
(5E0
, b13)
H
registration instruction
SB0020
Module status
(5E2
, b0)
H
SB0040
Data link restart
(5E4
, b0)
acceptance
H
SB0041
Data link restart
(5E4
, b1)
complete
H
Refresh instruction
SB0042
acknowledgement
(5E4
, b2)
status at standby
H
master switching
Refresh instruction
SB0043
complete status at
(5E4
, b3)
standby master
H
switching
SB0044
Data link stop
(5E4
, b4)
acceptance
H
SB0045
Data link stop
(5E4
, b5)
complete
H
Forced master
SB0046
switching
(5E4
, b6)
H
executable status
Temporary error
SB0048
invalid acceptance
(5E4
, b8)
H
status
Temporary error
SB0049
invalid complete
(5E4
, b9)
H
status
1: Can be used for the standby master station only.
3: Parameter setting is required in the case of a standby master station.
App - 23
Description
Executes loop tests for the stations specified by SW0008.
OFF: Not requested
ON : Requested
Reads the parameter setting information for the actual system
configuration.
(enabled only on Ver.1 remote stations)
OFF: Not requested
ON : Requested
Use this to perform the transmission speed test.
OFF: Not requested
ON : Requested
Forcefully transfers the data link control from the standby master
station that is controlling the data link to the standby master station in
case the standby master station becomes faulty.
OFF: Not requested
ON : Requested
Starts the initial processing using the information registered during the
initialization procedure registration.
While SB000D is on, the refresh of the remote input/output and
remote registers stops.
OFF: Not instructed
ON : Instructed
Indicates the module access (module operation) status.
OFF: Normal (Module is operating normally)
ON : Abnormal (Module error has occurred)
Indicates the data link restart instruction acknowledgement status.
OFF: Not acknowledged
ON : Startup instruction acknowledged
Indicates the data link restart instruction acknowledgement
completion status.
OFF: Not complete
ON : Startup complete
Indicates whether or not the refresh instruction at standby master
switching have been acknowledged.
OFF: Not executed
ON : Instruction acknowledged
Indicates whether or not the refresh instruction at standby master
switching is complete.
OFF: Not executed
ON : Switching complete
Indicates the data link stop instruction acknowledgement status.
OFF: Not acknowledged
ON : Stop instruction acknowledged
Indicates the data link stop instruction acknowledgement completion
status.
OFF: Not complete
ON : Stop complete
Indicates whether the forced master switching (SB000C) signal can
be executed or not.
OFF: Cannot be executed.
ON: Can be executed.
Indicates the acknowledgement status of remote station temporary
error invalid instruction.
OFF: Not executed
ON : Instruction acknowledged
Indicates the acknowledgement completion status of remote station
temporary error invalid instruction.
OFF: Not executed
ON : Temporary error invalid station established/Specified station
number is invalid
Availability
(
: Available,
: Not available)
Online
Master station
Local station
1
3
1
(To the next page)
APPENDIXES
Offline
App - 23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

L26cpu-bt

Table of Contents