Error code
Error details
(hexadecimal)
Specified station number not
B303
set error
B304
Loop test error station detected
Specified station number
B306
setting error
B307
All stations data link error
Station number setting error
B308
(installation status)
B309
Station number overlap error
Loading/parameter
B30A
consistency error
Loading/parameter
B30B
consistency error
Standby master station
B30C
specification error
B30D
Initial status
B30E
Unsupported error
Temporary error invalid station
B30F
specification error
B310
Data link restart error
15 - 24
Cause of error occurrence (details)
The station number was not specified during
temporary error invalid request/temporary
error invalid cancel request.
An error was detected in a remote
station, intelligent device station or
standby master station when a loop test
was performed.
A station number other than the head
station number was specified during
temporary error invalid request/temporary
error invalid cancel request.
All stations were in data link error status
when one of the following requests was
made:
• SB0000 (data link restart)
• SB0002 (data link stop)
The station number of the slave station is
outside of the range between "1 and 64".
The station number of the connected
module was duplicated (including
number of occupied stations).
However, this excludes the duplicate
head station number.
The station types of the module are
different from parameter settings.
Example)
Connected
Parameter
module
setting
Remote
Remote I/O
device
Remote I/O
Intelligent
Remote
device
device
The mode is inconsistent between the
master station and a local or standby
master station.
• The modes of the master station and
standby master station are different.
The contents of the installation status
and network parameters do not match.
Master station switching was instructed
to a station other than the standby
master station.
Temporary error invalid station
specification, loop test request, or data
link stop/restart request, etc. was issued
before starting the link.
In the function started by SB/SW, an
attempt was made to execute the
function, which is
supported by only the master station, at
the local station.
A temporary error invalid station was
specified while the data link is being
performed upon automatic CC-Link
startup.
Data link restart (SB0000) was executed
for the station that was performing a data
link.
Corrective action
Set a specified station number.
(SW0003, SW0004 to SW0007)
Check that the remote station,
intelligent device station or
standby master station is
operational and that the cable is
not disconnected.
Specify a head station when
temporary error invalid
request/temporary error invalid
cancel request is requested.
Request again after the data
link becomes normal.
Set the station number of the
slave station within the range
between "1 and 64".
Check the module station
number.
Set the correct parameters .
After correcting the parameters
of the master station, or the
local or standby master station,
reset the programmable
controller CPU.
Set the contents of the
installation status and network
parameters to match.
Specify the station number that
corresponds to the standby
master station.
Issue the request after the data
link is started.
Execute the corresponding
function from the master
station.
Specify a temporary error
invalid station while the data
link is performed with
parameters set using GX
Works2 or the dedicated
instruction.
Execute Data link restart
(SB0000) for the station that
has stopped a data link with
Data link stop (SB0002).
15 TROUBLESHOOTING