3. SIGNALS AND WIRING

3.3 Explanation of power supply system

3.3.1 Signal explanations

Connection target
Symbol
(application)
Main circuit power
L1/L2/L3
supply
Power factor
P3/P4
improving
DC reactor
P+/C/D
Regenerative option
Control circuit power
L11/L21
supply
POINT
For the layout of connector and terminal block, refer to chapter 9 DIMENSIONS.
Supply the following power to L1, L2, and L3. For 1-phase 200 V AC to 240 V AC, connect the
power supply to L1 and L3. Leave L2 open.
Servo amplifier
Power
3-phase 200 V AC to 240
V AC, 50 Hz/60 Hz
1-phase 200 V AC to 240
V AC, 50 Hz/60 Hz
3-phase 380 V AC to 480
V AC, 50 Hz/60 Hz
When not using the power factor improving DC reactor, connect P3 and P4(factory-wired).
When using the power factor improving DC reactor, disconnect P3 and P4, and connect the
power factor improving DC reactor to P3 and P4.
Refer to section 11.11 for details.
(1) 200 V class
1) MR-J4-500A(-RJ) or less
When using a servo amplifier built-in regenerative resistor, connect P+ and D (factory-
wired).
When using a regenerative option, disconnect P+ and D, and connect the regenerative
option to P+ and C.
2) MR-J4-700A(-RJ) to MR-J4-22KA(-RJ)
MR-J4-700A(-RJ) to MR-J4-22KA(-RJ) do not have D.
When using a servo amplifier built-in regenerative resistor, connect P+ and C (factory-
wired).
When using a regenerative option, disconnect wires of P+ and C for the built-in
regenerative resistor. And then connect wires of the regenerative option to P+ and C.
(2) 400 V class
1) MR-J4-350A4(-RJ) or less
When using a servo amplifier built-in regenerative resistor, connect P+ and D. (factory-
wired)
When using a regenerative option, disconnect P+ and D, and connect the regenerative
option to P+ and C.
2) MR-J4-500A4(-RJ) to MR-J4-22KA4(-RJ)
MR-J4-500A4(-RJ) to MR-J4-22KA4(-RJ) do not have D.
When using a servo amplifier built-in regenerative resistor, connect P+ and C. (factory-
wired)
When using a regenerative option, disconnect wires of P+ and C for the built-in
regenerative resistor. And then connect wires of the regenerative option to P+ and C.
Refer to section 11.2 to 11.5 for details.
Supply the following power to L11 and L21.
Servo amplifier
Power
1-phase 200 V AC to 240 V AC
1-phase 380 V AC to 480 V AC
Description
MR-J4-10A(-RJ) to
MR-J4-100A(-RJ) to
MR-J4-70A(-RJ)
MR-J4-22KA(-RJ)
L1/L2/L3
L1/L3
MR-J4-10A(-RJ) to
MR-J4-22KA(-RJ)
L11/L21
3 - 20
MR-J4-60A4(-RJ) to
MR-J4-22KA4(-RJ)
L1/L2/L3
MR-J4-60A4(-RJ) to
MR-J4-22KA4(-RJ)
L11/L21