11. OPTIONS AND AUXILIARY EQUIPMENT
(3) Connection diagram
(a) 200 V class
(Note 7)
MCCB
3-phase
200 V AC to
230 V AC
Note 1. Configure a sequence that will shut off main circuit power at the follow cases.
FR-CV or servo amplifier alarm occurs.
EM1 (forced stop 1) turns off.
2. For the servo amplifier, configure a sequence that will switch the servo-on after the FR-CV is ready.
3. For the FR-CV, the RSO signal turns off when it is put in a ready-to-operate status where the reset signal is input. Configure a
sequence that will make the servo inoperative when the RSO signal is on.
4. Configure a sequence that will make a stop with the emergency stop input of the servo system controller if an alarm occurs in
the FR-CV.
5. When using FR-CV, always disconnect wiring between P3 and P4 terminals.
6. Set [Pr. PA04] to "0 0 _ _" to enable EM1 (Forced stop 1).
7. When wires used for L11 and L21 are thinner than wires used for L1, L2, and L3, use a molded-case circuit breaker.
8. The illustration of the 24 V DC power supply is divided between input signal and output signal for convenience. However, they
can be configured by one.
POINT
In this configuration, only the STO function is supported. The forced stop
deceleration function is not available.
FR-CVL
MC
R/L11
R2/L12
S/L21
S2/L22
T/L31
T2/L32
RESET
(Note 1)
RA1
RA2 EM1
OFF
ON
MC
MC
SK
FR-CV
R2/L1
S2/L2
T2/L3
P/L+
N/L-
24 V DC (Note 8)
R/L11
S/L21
P24
T/MC1
SD
RES
(Note 2)
RDYB
RA3
SD
RDYA
A
(Note 1)
RA1
B
C
RA3
RA1
(Note 3)
RSO
SE
24 V DC (Note 8)
11 - 44
Servo amplifier
L11
U
L21
V
W
CN2
P4
(Note 5)
N-
24 V DC (Note 8)
DOCOM
ALM
SON
(Note 2)
SON
(Note 4)
EM1
EM1
(Note 1, 6)
RES
DICOM
Servo motor
U
V
W
(Note 1)
RA2