11. OPTIONS AND AUXILIARY EQUIPMENT
(2) For control circuit power supply
When the wiring for the control circuit power supply (L11, L21) is thinner than that for the main circuit
power supply (L1, L2, L3), install an overcurrent protection device (molded-case circuit breaker or fuse)
to protect the branch circuit.
Molded-case circuit breaker (Note)
Servo amplifier
Frame, rated current
MR-J4-10A(-RJ)
MR-J4-20A(-RJ)
MR-J4-40A(-RJ)
MR-J4-60A(-RJ)
MR-J4-70A(-RJ)
MR-J4-100A(-RJ)
MR-J4-200A(-RJ)
30 A frame 5 A
MR-J4-350A(-RJ)
MR-J4-500A(-RJ)
MR-J4-700A(-RJ)
MR-J4-11KA(-RJ)
MR-J4-15KA(-RJ)
MR-J4-22KA(-RJ)
MR-J4-60A4(-RJ)
MR-J4-100A4(-RJ)
MR-J4-200A4(-RJ)
MR-J4-350A4(-RJ)
MR-J4-500A4(-RJ) 30 A frame 5 A
MR-J4-700A4(-RJ)
MR-J4-11KA4(-RJ)
MR-J4-15KA4(-RJ)
MR-J4-22KA4(-RJ)
Note. When having the servo amplifier comply with the IEC/EN/UL/CSA standard, refer to appendix 4.
Fuse (Class T)
Voltage AC [V]
Current [A]
240
1
480
1
11 - 61
Fuse (Class K5)
Voltage AC [V]
Current [A]
300
1
600
1
Voltage AC [V]
250
600