2. Preparation for Installation

2.6 Leakage current

The Switch is equipped with a noise filter to prevent failure due to electric noise. As
a result, a maximum leakage current of 3.5 mA flows through the protective ground
line (Type D grounding).
Be sure to consider whether the installation of a residual current circuit breaker is
required for compliance with the Fire Service Act or other legislation.