NOTE
Generally, the breaker operating current is greater than the rated
current. Check the specifications of the circuit breaker.
In addition, if a Switch is turned on, the inrush current described in Table 2-12 Inrush
current flows. Consider measures for avoiding a voltage drop in the power supply
facility caused by the inrush current. Be especially careful, when using a UPS or
CVCF.
Table 2-12 Inrush current
Current
80 A
CAUTION
When a Switch is turned on, inrush current flows. Consider measures
for avoiding a voltage drop in the power supply facility caused by the
inrush current. Voltage drops affect not only the Switch, but also the
devices connected to the same power supply facility.
The inrush current described above is the value for a single power
NOTE
supply unit.
Time
40 ms