Figure 2-8 0 V and −48 V terminals
(1) 17.8 mm (max)
(2) 17.5 mm (max)
(3) 6.3 to 6.9 mm
(4) Insulation cover
Place an insulation cover over the 0 V and -48 V terminals. Using the
terminals without an insulation cover could result in fire or electric
shock. Place the insulation cover so that the distance from the hole of
the terminal to the insulation cover is 17.5 mm or less (half of the width
of the terminal board for the power supply unit). Be careful that the
exposed core of the cable does not extend out of the terminal board.
Figure 2-9 Ground terminal
(1) 17.8 mm (max)
(2) 6.3 to 6.9 mm
(3) 19 mm (max)
(4) 8 mm (max)
(5) 16 mm
2. Preparation for Installation
61