12. OPTIONS AND AUXILIARY EQUIPMENT

12.5 Power regeneration common converter

When using the power regeneration common converter, set parameter No. PA02 to "
(1) Model
(2) Selection
The power regenerative common converter FR-CV can be used for the servo amplifier of 200VAC class
with 750W to 22kW and that of 400VAC class with 11kW to 22kW. The following shows the restrictions on
using the FR-CV(-H).
(a) Up to six servo amplifiers can be connected to one FR-CV(-H).
(b) FR-CV(-H) capacity [W] Total of rated capacities [W] of servo amplifiers connected to FR-CV(-H).
(c) The total of used servo motor rated currents should be equal to or less than the applicable current [A] of
the FR-CV(-H).
(d) Among the servo amplifiers connected to the FR-CV(-H), the servo amplifier of the maximum capacity
should be equal to or less than the maximum connectable capacity [W].
The following table lists the restrictions.
Item
Maximum number of connected servo amplifiers
Total of connectable servo amplifier capacities [kW]
Total of connectable servo motor rated currents [A]
Maximum servo amplifier capacity [kW]
POINT
Use the FR-CV for the servo amplifier of 200VAC class and the FR-CV-H for
that of 400 VAC class.
For details of the power regeneration common converter FR-CV(-H), refer to the
FR-CV(-H) Installation Guide (IB(NA)0600075).
Do not supply power to the main circuit power supply terminals (L
servo amplifier. Doing so will fail the servo amplifier and FR-CV(-H).
Connect the DC power supply between the FR-CV(-H) and servo amplifier with
correct polarity. Connection with incorrect polarity will fail the FR-CV(-H) and
servo amplifier.
Two or more FR-CV(-H)'s cannot be installed to improve regeneration capability.
Two or more FR-CV(-H)'s cannot be connected to the same DC power supply
line.
Capacity
Capacity [kW]
Symbol
7.5k
7.5
11k
11
15k
15
22k
22
30k
30
37k
37
55k
55
Voltage class
Symbol
None
200VAC class
H
400VAC class
7.5K
11K
15K
3.75
5.5
7.5
33
46
61
3.5
5
7
12 - 39
, L
1
2
01".
FR-CV-
22K
30K
37K
6
11
15
18.5
90
115
145
11
15
15
, L
) of the
3
55K
27.5
215
22