12. OPTIONS AND AUXILIARY EQUIPMENT

12.13 Power factor improving DC reactor

The power factor improving DC reactor increases the form factor of the servo amplifier's input current to
improve the power factor. It can decrease the power supply capacity. As compared to the power factor
improving AC reactor (FR-BAL), it can decrease the loss. The input power factor is improved to about 95%.
It is also effective to reduce the input side harmonics.
When connecting the power factor improving DC reactor to the servo amplifier, always disconnect the wiring
across P
-P
(For 11kW or more, disconnect the wiring across P-P
1
2
power factor improving DC reactor is not produced.
When used, the power factor improving DC reactor generates heat. To release heat, therefore, leave a 10cm
or more clearance at each of the top and bottom, and a 5cm or more clearance on each side.
Rating plate
Terminal box - screw size G
E
A or less
2-F
L notch
Note 1. Since the terminal cover is supplied, attach it after connecting a wire.
2. When using DC reactor, disconnect the wiring across P
3. When over 11kW, "P
Power Factor
Servo Amplifier
Improving DC
Reactor
MR-J3-10A
20A
FR-BEL-0.4K
MR-J3-40A
FR-BEL-0.75K
MR-J3-60A
70A
FR-BEL-1.5K
MR-J3-100A
FR-BEL-2.2K
MR-J3-200A
FR-BEL-3.7K
MR-J3-350A
FR-BEL-7.5K
MR-J3-500A
FR-BEL-11K
MR-J3-700A
FR-BEL-15K
MR-J3-11KA
MR-J3-15KA
FR-BEL-22K
MR-J3-22KA
FR-BEL-30K
MR-J3-60A4
FR-BEL-H1.5K
MR-J3-100A4
FR-BEL-H2.2K
MR-J3-200A4
FR-BEL-H3.7K
MR-J3-350A4
FR-BEL-H7.5K
MR-J3-500A4
FR-BEL-H11K
MR-J3-700A4
FR-BEL-H15K
MR-J3-11KA4
MR-J3-15KA4
FR-BEL-H22K
MR-J3-22KA4
FR-BEL-H30K
POINT
For the 100VAC power supply type (MR-J3- A1), the power factor improving
DC reactor cannot be used.
Servo amplifier
FR-BEL-(H)
P
(Note 2)
P
5m or less
H
B or less
Mounting leg
F
Fig. 12.1
" becomes "P", respectively.
2
Outline
drawing
A
B
110
50
120
53
130
65
Fug. 12.1
130
65
150
75
150
75
170
93
170
93
Fig. 12.2
185
119
185
119
130
63
130
63
Fig. 12.1
150
75
150
75
170
93
170
93
Fig. 12.2
185
119
185
119
). If it remains connected, the effect of the
1
Rating plate
Screw size G
1
2
E
A or less
2-F
-P
.
1
2
Dimensions [mm]
C
D
E
F
L
94
1.6
95
6
12
102
1.6
105
6
12
110
1.6
115
6
12
110
1.6
115
6
12
102
2.0
135
6
12
126
2.0
135
6
12
132
2.3
155
6
14
170
2.3
155
6
14
182
2.6
165
7
15
201
2.6
165
7
15
89
1.6
115
6
12
101
1.6
115
6
12
102
2
135
6
12
124
2
135
6
12
132
2.3
155
6
14
160
2.3
155
6
14
171
2.6
165
7
15
189
2.6
165
7
15
12 - 65
(Note 1)Terminal cover
FR-BEL-(H)
H
B or less
L notch
Mounting leg
F
Fig. 12.2
Mounting
Screw Size
G
H
M3.5
25
M5
M4
25
M5
M4
30
M5
M4
30
M5
M4
40
M5
M5
40
M5
M5
50
M5
M8
56
M5
M8
70
M6
5.4(11.91)
M8
70
M6
6.7(14.77) 60(AWG2/0)
M3.5
32
M5
M3.5
32
M5
M4
40
M5
M4
40
M5
M5
50
M5
M6
56
M5
M6
70
M6
5.0(11.02)
M6
70
M6
6.7(14.77)
Servo amplifier
P
1
(Note 3)
(Note 2)
P
2
5m or less
Used Power
Mass
Supply
[kg(lb)]
2
[mm
]
0.5(1.10)
0.7(1.54)
1.1(2.43)
2(AWG14)
1.2(2.65)
1.7(3.75)
2.3(5.07)
3.5(AWG12)
3.1(6.83)
5.5(AWG10)
8(AWG8)
3.8(8.38)
22(AWG4)
30(AWG2)
0.9(1.98)
1.1(2.43)
2(AWG14)
1.7(3.75)
2.3(5.07)
3.1(6.83)
5.5(AWG10)
3.7(8.16)
8(AWG8)
22(AWG4)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents