14. ABSOLUTE POSITION DETECTION SYSTEM
(2) Sequence program example
(a) Conditions
1) When the servo-on signal and power supply GND are shorted, the ABS data is transmitted at power-
on of the servo amplifier or on the leading edge of the RUN signal after a PC reset operation (PC-
RESET). The ABS data is also transmitted when an alarm is reset or when an emergency stop is
reset.
2) If a checksum mismatch is detected in the transmitted data, data transmission is retried up to three
times. If the checksum mismatch still persists after the retries, the ABS checksum error occurs (Y3A
ON).
3) The following time periods are measured. If the ON/OFF state does not change within the specified
time, the ABS communication error occurs change within the specified time, the ABS communication
error occurs (Y3A ON):
ON period of ABS transfer mode (Y31)
ON period of ABS request (Y32)
OFF period of reading to send ABS data (X22)
(b) Device list
X20
ABS Transmission data bit 0 / positioning
completion
X21
ABS Transmission data bit 1 / zero speed
X22
Reading to send ABS data / limiting torque
X23
Servo alarm
X24
Alarm reset
X25
Servo emergency stop
X26
Servo-on
X27
Home position return start
X28
Operation mode I
X29
Operation mode II
D0
ABS data transmission counter
D1
Checksum transmission counter
D2
Checksum addition register
D3
ABS data: Lower 16 bits
D4
ABS data: Upper 16 bits
D5
ABS data 2-bit receiving buffer
D6
Check data in case of checksum error
D7
Number of retries
D8
Forward rotation direction
D9
Home position address: Lower 16 bits
D10
Home position address: Upper 16 bits
D11
Drive unit ready data
D12
Home position return completion data
D110
Received shift data: Lower 16 bits
D111
Received shift data: Upper 16 bits
T0
ABS transmission mode timer
T1
ABS request response timer
T2
Retry wait timer
T3
ABS data send reading response timer
T10
Clear (CR) ON timer
(Note 1)
T200
Transmitted data read 10ms delay timer
Note 1. Required for data set type home position return.
2. Required for electromagnetic brake output.
X input contact
D register
T timer
Y output contact
Y30
Servo-on
Y31
ABS transfer mode
Y32
ABS request
Y33
Alarm reset
X34
Electromagnetic brake output
(Note 2)
Y35
Clear
(Note 1)
Y38
Servo alarm
Y39
ABS communication error
Y3A
ABS checksum error
M5
ABS data transmission start
M6
Sum check completion
M7
Sum check mismatch
M8
ABS data ready
M9
Transmission data read enabled
M10
Checksum 2 bits read completion
M11
ABS 2 bits read completion
M12
ABS 2 bits request
M13
Servo-on request
M14
Servo alarm
M15
ABS data transmission retry start pulse
M16
Retry flag set
M17
Retry flag reset
M18
PLS processing command
M20
Clear (CR) ON timer request
(Note 1)
M21
Data set type home position return request
(Note 1)
M22
Home position return processing instruction
M23
Current position change processing
instruction
M24
Current position change flag
C0
ABS data receive times counter
C1
Checksum receive times counter
C2
Retry counter
14 - 35