Ê Perform the following procedures:
1.
"Opening the rack door" on page 59
2.
"Locating the defective server" on page 55
3. If applicable, ensure to note down your current network settings in the
operating system.
4.
"Disabling SVOM boot watchdog functionality" on page 76
5.
"Disabling BitLocker functionality" on page 75
6.
"Shutting down the server" on page 59
7. Disconnect all external cables.
8.
"Extending/removing the server from the rack" on page 60
9.
"Opening the server" on page 64
10. Remove all memory modules, see section
module" on page
I
Before removing the memory modules, take a note on the
installation slot number for each memory module. Make sure that
you reinstall the memory modules in the slot they were located
before the replacement.
11. Remove the air duct, see section
12. Remove the heat sink, see section
page
283.
13. Remove all expansion cards, see section
modules" on page
I
Before removing the expansion cards, take a note on the
installation slot number for each card. Make sure that you reinstall
the card in the slot it was located before the replacement.
14. Remove the front LAN card (if applicable), see section
defective front LAN card" on page
15. Remove the UFM (if applicable), see section
UFM" on page
I
Remove the UFM spacer from the defective system board and
fasten it with the UFM screw to the UFM board.
RX100 S7
275.
199.
359.
Upgrade and Maintenance Manual
System board and components
"Removing a memory
"Removing the air duct" on page
"Removing the heat sink" on
"Expansion cards and riser
343.
"Removing the defective
282.
"Removing the
377