The Function 0x02 is implemented for this variable.
Variables available from version C11.1006.230203.
(9)
8�3�9�- DEVICE CONFIGURATION VARIABLES
The Functions 0x04 and 0x10 are implemented for this variable.
The device's Modbus function does not check whether the variables recorded are within the correct
margins, they are only checked when they are read from the EEPROM. So if any parameter is recorded
with an incorrect value the device will be configured with its default value.
The Modbus configuration will not take effect until the device is reset.
8�3�9�1�- Transformation ratios�
Configuration variable
Voltage primary
Voltage secondary
Current primary
Current secondary
All variables must be programmed at the same time.
(10)
Voltage ratio x Current ratio < 600000.
(11)
Parameter not available in model CVM-C11-FLEX-IN-485-ICT2.
(12)
Only available for models CVM-C11-ITF-IN-xxx-ICT2�
(13)
Note: The ratio is between the primary and the secondary.
8�3�9�2�- Neutral current transformation ratios
Configuration variable
Neutral current primary
Neutral current secondary
All variables must be programmed at the same time.
(14)
Parameter not available in model CVM-C11-FLEX-IN-485-ICT2.
(15)
Only available for models CVM-C11-ITF-IN-xxx-ICT2�
(16)
106
Table 83: Modbus memory map: Status of digital inputs�
Status of digital inputs
(9)
Variable
Digital input 1
Digital input 2
Table 84: Modbus memory map: Transformation ratios�
(10) (11)
(12)
(13)
Table 85: Modbus memory map: Neutral current transformation ratios�
(14)
(15)
(16)
Address
0
1
Transformation ratios
Address
2710 - 2711
2712
2713
2714
Transformation ratios
Address
271A
271B
Value
0: Disabled - 1: Enabled
0: Disabled - 1: Enabled
Valid data margin
1 - 599999
1 - 999
1 - 10000
1: .../1A
5: ../5 A
Valid data margin
1 - 10000
1: .../1A
5: ../5 A
Instruction Manual
CVM-C11
Default
value
1
1
5
5
Default
value
5
5