CVM-C11
All variables must be programmed at the same time.
(21)
They have 4 decimal place.
(22)
8�3�9�13�- Programming alarms 1 and 2 (Relays 1 and 2)
Configuration variable
Maximum value
Minimum value
Variable code
Connection delay
Hysteresis
latch
Disconnection delay
Contacts status
8�3�9�14�- Programming alarms 3 and 4 (Digital outputs T1 and T2)
Configuration variable
Kilowatts per impulse
Variable code
Pulse width
8�3�9�15�- Digital inputs
Configuration variable
Operating mode
(23)
If Input 1 is configured as a tariff and Input 2 is configured as a logic state (or vice versa) we will only have
(23)
2 tariffs.
Option available on digital input 1.
(24)
We can also read the status of the digital inputs when they are in logic mode:
The Function 0x04 is implemented for this variable.
Instruction Manual
Table 96: Modbus memory map: Programming alarms 1 and 2�
Programming alarms 1 and 2
Address
Relay 1
Relay 2
2AF8-2AF9
2B02-2B03
2AFA-2AFB
2B04-2B05
2AFC
2AFD
2AFE
2AFF
2B00
2B01
Table 97: Modbus memory map: Programming alarms 3 and 4�
Programming alarms 3 and 4
Address
Relay 1
Relay 2
2B0C-2B0D
2B16-2B17
2B10
2B1A
2B11
2B1B
Table 98: Modbus memory map: Configuration of digital inputs�
Address
Input 1
Input 2
2B66
2B67
2: Maximum demand synchronism pulse
Valid data margin
depending on the variable
depending on the variable
2B06
Table 48 and Table 49
2B07
0 - 9999 seconds
2B08
0 - 99 %
0 : No
2B09
1: Yes
0 - 9999 seconds
2B0A
0 : Normally open
2B0B
1: Normally closed
Valid data margin
Table 57
Table 48, Table 49 and Table
56
30 - 400 ms
Valid data margin
0: Tariff
1: Logic state
Default
value
0
0
0
0
0
0
0
0
Default
value
0
0
100 ms
Default
value
0
(24)
109