8�3�9�18�- Password configuration
These variables allow you to lock or unlock access to the programming menu, and also allow you to
change the password code. The password code may only be changed through this command.
The device does not need you to enter the old password in order for it to record the new one; it records
the new one directly without any verification.
Password
Configuration variable
Password value
(28)
Lock-Unlock
You must program all the variables at the same time.
(27)
The password value is read and written in hexadecimal.
(28)
8�3�9�19�- Ethernet Communications
Note: Ethernet communications are available on model CVM-C11-ITF-IN-ETH-ICT2.
Configuration variable
Ethernet protocol
Modbus TCP: DHCP
Modbus TCP: IP adress
Modbus TCP: Mask
Modbus TCP: Gateway
Modbus TCP: MAC adress
Modbus TCP: Port
BACnet: Port
This parameter cannot be modified.
(29)
8�4�- BACnet PROTOCOL
BACnet is a communications protocol for Building Automation and Control NETworks. This protocol
replaces the proprietary communications of each device, making it a set of common communication
rules that enables the complete integration of the building automation and control devices of different
manufacturers.
The device features BACNet MS/TP communications, following the specifications of ANSI/ASHRAE
135 (ISO 16484-5).
Instruction Manual
Table 104: Modbus memory map: Password configuration
Address
(27)
2B70
2B71
Table 105: Modbus memory map: Ethernet communications�
Ethernet communications
Address
2800
2801
2802 - 2803 -
2804 - 2805
2806 - 2807 -
2808 - 2809
280A - 280B -
280C - 280D
280E - 280F -
2810 - 2811 -
(29)
2812 - 2813 -
2814
2815
Valid data margin
0 - 9999
0: Unlock
1: Lock
Valid data margin
0: Modbus TCP
1: BACnet IP
0: No, DHCP not enabled
1: Yes, DHCP enabled
0�0�0�0� - 255�255�255�255
0�0�0�0� - 255�255�255�255
0�0�0�0� - 255�255�255�255
-
1 - 65535
1 - 65535
Default value
1234
0
Default value
0
1
010.002.004.233
255.255.255.000
010.002.004.001
00A2A2A2A201
502
47808
111