CVM-C5-xxx-485 3�- UNIT INSTALLATION 3�1�-PRIORRECOMMENDATIONS Inordertousethedevicesafely,itiscriticalthatindividualswhohandleitfollow thesafetymeasuresdescribedinthestandardsofthecountrywhereitisbeing used,usethenecessarypersonalprotectiveequipment,andpayattentiontothe variouswarningsindicatedinthisinstructionmanual� TheCVM-C5devicemustbeinstalledbyauthorisedandqualifiedstaff� The power supply plug must be disconnected and measuring systems switched off before handling,alteringtheconnectionsorreplacingthedevice�Itisdangeroustohandlethedevice whileitispowered� Also,itiscriticaltokeepthecablesinperfectconditioninordertoavoidaccidents,personal injuryanddamagetoinstallations� Themanufacturerofthedeviceisnotresponsibleforanydamageresultingfromfailurebythe userorinstallertoheedthewarningsand/orrecommendationssetoutinthismanual,norfor damageresultingfromtheuseofnon-originalproductsoraccessoriesorthosemadebyother manufacturers� Intheeventananomalyormalfunctionisdetectedinthedevice,refrainfromusingittotake anymeasurements� Inspecttheworkareabeforetakinganymeasurements�Donottakemeasurementsindanger- ousareasorwherethereisariskofexplosion� Disconnect the device from the power supply (device and measuring system powersupply)beforemaintaining,repairingorhandlingthedevice'sconnections� Pleasecontacttheafter-salesserviceifyoususpectthatthereisanoperational faultinthedevice�...
CVM-C5-xxx-485 3�4�-CONNECTIONDIAGRAMS 3�4�1�- THREE-PHASE NETWORK MEASURING WITH A 4-WIRE CONNECTION, MODEL CVM-C5-IFF-485 AND CVM-C5-mV-485� Measurementsystem: Power Supply OUTPUT RS485 POWER SUPPLY S0+ S0- Ph-Ph Ph-N 520V ~ 300V ~ P2 P1 LOAD Figure 3:Three-phase measuring with a 4-wire connection, model CVM-C5-ITF-485 and CVM-C5-mV-485� Instruction Manual...
CVM-C5-xxx-485 3�4�5�- THREE-PHASE NETWORK MEASURING WITH A 3-WIRE CONNECTION AND TRANSFORMERS IN AN ARON CONNECTION� Measurementsystem: Power Supply OUTPUT RS485 POWER SUPPLY S0+ S0- Ph-Ph Ph-N 520V ~ 300V ~ P2 P1 LOAD Figure 7: Three-phase measuring with a 3-wire connection and transformers in an ARON connection� Instruction Manual...
CVM-C5-xxx-485 4�3�-DISPLAY ThedevicehasabacklitLCDdisplayshowingalltheparameterslistedinTable 4. Thedisplayisdividedintotwoareas( Figure 12 Theconsumption dataareashowingconsumptionparameters� Theinstantaneous dataareashowingthemaximumandminimuminstantaneous valuesbeingmeasuredorcalculatedbythedevice� Figure 12: CVM-C5 display areas� 4�3�1� CONSUMPTION DATA AREA Thedevicehas22differentscreensintheconsumptiondataarea( )� Table 7 Table 7: Consumption data area screens� Screen Units TotalactiveenergygeneratedTariff1 InductivereactiveenergygeneratedTariff1 kvar CapacitivereactiveenergygeneratedTariff1 kvar Instruction Manual...
Page 22
CVM-C5-xxx-485 Table 7 (Continuation): Consumption data area screens� Screen Units TotalapparentenergygeneratedTariff1 kVAh EmissionsTariff1 kgCO CostTariff1 COST No�ofhoursTariff1 hours TotalactiveenergyconsumedTariff1 InductivereactiveenergyconsumedTariff1 kvar CapacitivereactiveenergyconsumedTariff1 kvar TotalapparentenergyconsumedTariff1 kVAh TotalactiveenergygeneratedTariff2 InductivereactiveenergygeneratedTariff2 kvar CapacitivereactiveenergygeneratedTariff2 kvar TotalapparentenergygeneratedTariff2 kVAh Instruction Manual...
Page 23
CVM-C5-xxx-485 Table 7 (Continuation): Consumption data area screens� Screen Units EmissionsTariff2 kgCO2 CostTariff2 COST No�ofhoursTariff2 hours TotalactiveenergyconsumedTariff2 InductivereactiveenergyconsumedTariff2 kvar CapacitivereactiveenergyconsumedTariff2 kvar TotalapparentenergyconsumedTariff2 kVAh With the keywecanbrowsebetweenthedifferentscreens� ThesymbolsT1andT2thatappearonthedisplayindicatetheselectedtariffandthetariffbeing displayed,accordingto Table 10� Instruction Manual...
CVM-C5-xxx-485 4�6�4� SECONDARY CURRENT (ONLY THE MODEL CVM-C5-ITF-485) Onthisscreenthecurrenttransformersecondaryisselected� Usethe keytojumpbetweenthetwopossibleoptionsfor thecurrenttransformersecondary(1Aor5A)� Tovalidatetheinformationandgotothenextprogrammingstep,press � Note: Ifthevoltageratiotogetherwiththeprogrammedcurrentratioexceedsthemaximum power value that can be measured by the device, it will return to the primary voltage programmingstepwhenyoupressthe key� Nota : To apply the change to the second current transformer is necessary to reset the computer. 4�6�5�...
CVM-C5-xxx-485 4�6�6� RATIO OF KGC0 CARBON EMISSIONS FOR TARIFF 1 Thecarbonemissionsratioistheamountofemissionsreleased intotheatmospheretoproduceaunitofelectricity(1kWh)� TheratiofortheEuropeanmixisapproximately0�65kgCO per kWh� Toenterormodifytheemissionsratiovalue,pressthe key repeatedly,increasingthevalueoftheflashingdigit� Whentheon-screenvalueisthatdesired,pressthe keytogotothenextdigittomodify theothervalues� Ifyoupressthe keyafterchangingthelastdigit,itwilljumpbacktothefirstdigitsoyou canmodifythepreviouslyprogrammedvaluesagain� Tovalidatetheinformationandgotothenextprogrammingstep,press � Ifthevalueenteredisgreaterthanthemaximumprogrammingvalue,thedigitsflashfor2 secondsandtheprogrammedvalueisdeleted� Maximum programming value: 9.999. Minimum programming value: 0. 4�6�7� COST RATIO FOR TARIFF 1 On this screen the cost per kWh of electricity of Tariff 1 is programmed�...
CVM-C5-xxx-485 4�6�8� RATIO OF KGCO CARBON EMISSIONS FOR TARIFF 2 Thecarbonemissionsratioistheamountofemissionsreleased intotheatmospheretoproduceaunitofelectricity(1kWh)� TheratiofortheEuropeanmixisapproximately0�65kgCO per kWh� Toenterormodifytheemissionsratiovalue,pressthe key repeatedly,increasingthevalueoftheflashingdigit� Whentheon-screenvalueisthatdesired,pressthekeytogotothenextdigit tomodifytheothervalues� Ifyoupressthe keyafterchangingthelastdigit,itwilljumpbacktothefirstdigitsoyou canmodifythepreviouslyprogrammedvaluesagain� Tovalidatetheinformationandgotothenextprogrammingstep,press � Ifthevalueenteredisgreaterthanthemaximumprogrammingvalue,thedigitsflashfor2 secondsandtheprogrammedvalueisdeleted� Maximum programming value: 9.999. Minimum programming value: 0. 4�6�9� COST RATIO FOR TARIFF 2 On this screen the cost per kWh of electricity of Tariff 2 is programmed�...
CVM-C5-xxx-485 4�6�10� MAXIMUM DEMAND VARIABLE On this screen the variables to integrate into the Maximum Demandconceptareselected� The display shows the digits that identify that code for the variabletobeintegratedaccordingto Table 11 Table 11: Codes for maximum demand variables Parameter Code Activethree-phasepower Apparentthree-phasepower Three-phasecurrent CurrentL1,L2,L3...
CVM-C5-xxx-485 4�6�12� DELETING MAXIMUM DEMAND Onthisscreenyouselectwhetherornottodeletethemaximum demand� Usethe keytojumpbetweenthetwooptions(YesandNo)� Tovalidatetheinformationandgotothenextprogrammingstep, press � 4�6�13� DEFAULT SCREEN Onthisscreenthedefaultorstart-upinstantaneousdatascreen )fortheCVM-C5isselected� Table 8 Pressthe keyrepeatedlyuntilyouseethedefaultscreenof yourchoice� To validate the screen and go to the next programming step, press � The electrical parameters may also be displayed by automatically rotating through the 7 instantaneousdatascreensin5-secondintervals�...
CVM-C5-xxx-485 4�6�15� PROGRAMMING THE DIGITAL OUTPUT ( MODEL CVM-C-xxx-RS485-C ) TheCVM-C5digitaloutputmaybeprogrammedas: Pulse by n kWh or kvarh (Energy):thevaluecorrespondingtotheenergyconsumed orgeneratedmaybeprogrammed,togenerateapulse� Alarm condition:amagnitudemaybeassociatedwiththedigitaloutput,settinga maximum,minimumanddelayvalueforthetripcondition� Ifyoudonotwishtoprogramavariable,put00andvalidatewiththe key� Pulse programming by n kWh or kvarh Onthisscreentheenergycodeisselectedbasedon for Table 12...
Page 36
CVM-C5-xxx-485 Toenterormodifythekilowattsperpulsevalue,pressthe keyrepeatedly,increasingthevalueoftheflashingdigit� Whentheon-screenvalueisthatdesired,pressthe keyto gotothenextdigittomodifytheothervalues� Ifyoupressthe keyafterchangingthelastdigit,itwilljumpbacktothefirstdigitsoyou canmodifythepreviouslyprogrammedvaluesagain� Example: To program 500 Wh per pulse: 000.500 To program 1.5 kWh per pulse: 001.500 Oncethedesiredoptionhasbeenprogrammed,pressthe keytovalidatetheinformation andtherebyfinishprogrammingthedevice� Maximum programming value: 999999 KWh. Minimum programming value: 000.001 KWh. Programming by alarm condition Onthisscreentheparametercodeforwhichyouwantanalarm tobegeneratedisselected,basedonTable 13 �...
Page 38
CVM-C5-xxx-485 Thisiswherethedevice'sconnectionanddisconnectiondelay(in seconds)areprogrammed� Toenterormodifythedelayvalue,pressthe keyrepeatedly, increasingthevalueoftheflashingdigit� Whentheon-screenvalueisthatdesired,pressthe keyto gotothenextdigittomodifytheothervalues� Oncethedelayhasbeenprogrammed,pressthe keytogotothenextprogrammingstep� wecanseethefunctioningofthedigitaloutputbasedontheprogrammedmaxi- Table 15 mumandminimumvalues� Table 15: Functioning of the digital output based on the programmed maximum and minimum values� Maximum Minimum value Condition Digital output functioning value� Positive Positive MAX>MIN Positive Positive...
CVM-C5-xxx-485 4�6�16� DELETING ENERGY METERS Onthisscreenyouselectwhetherornottodeletetheenergy meters� Usethe keytojumpbetweenthetwooptions(YesandNo)� Tovalidatetheinformationandgotothenextprogrammingstep, press � 4�6�17� DELETING MAXIMUM AND MINIMUM VALUES Onthisscreenyouselectwhetherornottodeletethemaximum andminimumvalues Usethe keytojumpbetweenthetwooptions(YesandNo)� Tovalidatetheinformationandgotothenextprogrammingstep, press � 4�6�18� MODBUS COMMUNICATIONS : DEFAULT PARAMETERS On this screen you select whether we want to return to the defaultparametersoftheModbuscommunications�...
CVM-C5-xxx-485 4�6�23� MODBUS COMMUNICATIONS : NUMBER OF STOP BITS The number of Stop bits of Modbus communications are programmedonthisscreen� Presskey tobrowsetheoptions:1or2bits� Tovalidatetheinformationandgotothenextprogrammingstep, press � 4�6�24� LOCKING THE PROGRAMMING This screen is for protecting the data configured in the programmingmenu� Usethe keytojumpbetweenthetwooptions: Whenyouentertheprogrammingmenuyoucanviewandmodifytheprogramming� Whenyouentertheprogrammingyoucanviewtheprogrammingbutnotmodifyit��Inorder...
CVM-C5-xxx-485 4�7�2� PROTOCOL IntheModbusprotocol,theCVM-C5unitusestheRTU(RemoteTerminalUnit)mode� TheModbusfunctionsimplementedintheunitareasfollows: Function 03 and 04� ReadingnWords(2bytes)�Functionusedforreadingtheparameters beingmeasuredbytheCVM-C5�Allparametersare32-bitslong,whichiswhytoaskeach parametertakestwoWords� Function 10�Writingmultiplelogs� 4.7.2.1. Selecting the active tariff TheCVM-C5hastwotariffs,T1andT2,selectableusingthefollowingModbusfunction: Selecting the active tariff: Registro Address Function No registers No bytes Tariff inicial 1388 0001 000T xxxx NP: Peripheralnumber Theselectionoftheactivetariffisselectedaccordingtothefollowingtable: Table 16:Selecting tariff.
CVM-C5-xxx-485 5�- TECHNICAL FEATURES AC Power supply Rated voltage 95���240V~±10% Frequency 50���60Hz Consumption 3�5���6VA Installation category CATIII300V DC Power supply Rated voltage 105���272V ±10% Consumption 2���6W Installation category CATIII300V Voltage measurement circuit Nominal voltage (Un) 300V ,520V Voltage measurement margin 5���120%Un Frequency measurement margin 45���65Hz...
Page 48
CVM-C5-xxx-485 (Continuation) Pulse output (CVM-C5-xxx-RS485-C) Minimum pulse width 100ms(Ton:100ms,Toff:100ms) Digital input (CVM-C5-xxx-RS485-I) Type Potentialfreecontact Insulation Optoisolated MustbeconnectedtoSELVcircuit� User interface Display LCD(60x54mm) Keyboard 3keys Environmental features Operating temperature -5ºC���+45ºC Storage temperature -10ºC���+50ºC Relative humidity (non-condensing) 5���95% Maximum altitude 2000 m IP21 Protection degree Frontpanel:IP51 Thispollutiondegreehasn’tbeentestedbyUL�...