CIRCUTOR S�A�U� reserves the right to make modifications to the device or the unit specifications set out in this instruction manual without prior notice. CIRCUTOR S�A�U� on its web site, supplies its customers with the latest versions of the device specifi- cations and the most updated manuals.
- 5 plug-in connectors with screws, - 1 seal, If any problem is noticed upon reception, immediately contact the transport com- pany and/or CIRCUTOR's after-sales service. 2.- PRODUCT DESCRIPTION The CVM-B150 device measures, calculates and displays the main electrical parameters in single-phase networks, with and without neutral two-phase networks, balanced three-phase networks, with ARON measurement or unbalanced networks.
Page 9
CVM-B150-ITF-HF The CVM-B150 can be expanded with the following expansion modules: M-CVM-AB-8I-8OTR, expansion module with 8 transistor digital inputs and 8 transistor digital outputs. M-CVM-AB-8I-8OR, expansion module with 8 relay digital inputs and 8 relay digital outputs. M-CVM-AB-4AI-8AO, expansion module with 4 analogue inputs and 8 analogue out puts.
CVM-B150-ITF-HF 3.- DEVICE INSTALLATION 3�1�- PRIOR RECOMMENDATIONS In order to use the device safely, it is critical that individuals who handle it follow the safety measures set out in the standards of the country where it is being used, use the necessary personal protective equipment, and pay attention to the various warnings indicated in this instruction manual.
CVM-B150-ITF-HF cross-section of 1mm and the wires must to endure a temperature at least 77 degrees. The secondary line of the current transformer will have a minimum cross-section of 2.5 mm Current needs to be measured via external current transformers providing reinforced insulation.
CVM-B150-ITF-HF 3�3�2�- TERMINALS ON THE LOWER FACE Table 4:List of terminals on the lower face of the CVM-B150� Device terminals 25: S2, Current input L2 20 : , Auxiliary power supply. 26: S1 Current input L3 , Auxiliary power supply.
CVM-B150-ITF-HF 3�4�- CONNECTION DIAGRAMS 3�4�1�- THREE-PHASE NETWORK MEASUREMENT WITH A 4-WIRE CONNECTION� Measurement system: Secondary winding of the current transformer: Secondary winding of the neutral current transformer: P2 P1 POWER SUPPLY S1 S2 S1 S2 S1 S2 S1 S2 Power...
CVM-B150-ITF-HF 3�4�3�- THREE-PHASE NETWORK MEASUREMENT WITH A 3-WIRE CONNECTION AND 3 VOLTAGE TRANSFORMERS Measurement system: Secondary winding of the current transformer: P2 P1 POWER SUPPLY S1 S2 S1 S2 S1 S2 S1 S2 Power Supply P2 S1 P2 S1 LOAD Figure 5: Three-phase measuring with a 3-wire connection and 3 voltage transformers (transformer secondary: /1A, /5A)�...
CVM-B150-ITF-HF 3�4�4�- THREE-PHASE NETWORK MEASUREMENT WITH A 3-WIRE CONNECTION AND TRANSFORM- ERS WITH AN ARON CONNECTION� Measurement system: Secondary winding of the current transformer: P2P1 POWER SUPPLY S1 S2 S1 S2 S1 S2 S1 S2 Power Supply LOAD Figure 6: Three-phase measuring with a 3-wire connection and transformers in an ARON connection (transformer secondary: /1A, /5A)�...
CVM-B150-ITF-HF 3�4�5�- TWO-PHASE NETWORK MEASUREMENT WITH A 3-WIRE CONNECTION� Measurement system: Secondary winding of the current transformer: Secondary winding of the neutral current transformer: P2 P1 POWER SUPPLY S1 S2 S1 S2 S1 S2 S1 S2 Power Supply LOAD Figure 7: Two-phase measuring with a 3-wire connection (transformer secondary: /1A, /5A )�...
CVM-B150-ITF-HF 3�4�6�- SINGLE-PHASE NETWORK MEASUREMENT, PHASE TO PHASE, WITH A 2-WIRE CONNECTION� Measurement system: Secondary winding of the current transformer: P2 P1 POWER SUPPLY S1 S2 S1 S2 S1 S2 S1 S2 Power Supply LOAD Figure 8: Phase to phase single-phase measuring with a 2-wire connection (transformer secondary: /1A, /5A)�...
CVM-B150-ITF-HF 3�4�7�- SINGLE-PHASE NETWORK MEASUREMENT, PHASE TO NEUTRAL, WITH A 2-WIRE CONNEC- TION� Measurement system: Secondary winding of the current transformer: P2 P1 POWER SUPPLY S1 S2 S1 S2 S1 S2 S1 S2 Power Supply LOAD Figure 9: Phase to neutral single-phase measuring with a 2-wire connection (transformer secondary: /1A, /5A)�...
CVM-B150-ITF-HF 3�5�- STARTING UP THE DEVICE When the CVM-B150 has been powered up, the display will show the following screen , , while Figure 10 the device’s software is loading. Figure 10:Loading screen� If there has been an error in the start-up process, the device displays an error message. The possible...
Page 21
CVM-B150-ITF-HF When the graphic resources have loaded, the following screen appears, , appears on the dis- Figure 11 play and checks the integrity of the device and detects the expansion modules. Figure 11: Initial check screen of the CVM-B150� When the checking process has finished, the welcome screen is displayed (...
Page 22
CVM-B150-ITF-HF If this is the first time the device is switched on, the screen in appears to select the Figure 13 language. Figure 13: Language selection screen� The following options appear in the lower area: Con guration > < values <...
Page 23
CVM-B150-ITF-HF After selecting the language, select the current date ( Format: dd/mm/yyyy) and time ( Figure 15 Figure 15: Current date and time selection screen� The digit selected is indicated in white. The following options appear in the lower area: >...
Page 24
CVM-B150-ITF-HF Finally, select the corresponding time zone for the device, Figure 17 Figure 17: Time zone selection screen� The following options appear in the lower area: > > < < Con guration values Con rm Previous and save Next >...
Page 25
CVM-B150-ITF-HF The screen shown in will then be displayed for a few seconds, Figure 19 Figure 19: Start-up screen, CVM-B150� The device completes its start-up and the main screen is shown on the display, Figure 20 Figure 20: Main screen, CVM-B150�...
CVM-B150-ITF-HF 4.- OPERATION 4�1�- OPERATING PRINCIPLE The CVM-B150 is a four-quadrant power analyzer (consumption and generation). 90º kW + kW - kvarL PF + PF - kvarC kvar + Cos φ + Cos φ - kvar - 180º 0º kW -...
CVM-B150-ITF-HF 4�2�- MEASUREMENT PARAMETERS The device displays the electrical parameters shown in Table 6 Table 6: CVM-B150 measurement parameters� Phases Total Parameter Units L1-L2-L3 Phase-neutral voltage Vph-N Phase-phase voltage Vph-ph Current Frequency (L1)
CVM-B150-ITF-HF Table 6 (Continuation): CVM-B150 measurement parameters� Phases Total Parameter Units L1-L2-L3 Maximum Active Power Demand, Tariff 3 Maximum Apparent Power Demand, Tariff 3 Tariff: Parameter Units Total Tariff T1-T2-T3 No. of hours of active tariff hours ...
CVM-B150-ITF-HF 4�4�1�- UPPER AREA Figure 23: Upper area of display� The current date and time are displayed in real time in this area. The following are also displayed: Communications expansion module If a communications expansion module has been installed, one of the following messages will be dis-...
CVM-B150-ITF-HF Consumption or Generation The icon indicates that the installation is generating. The icon indicates that the installation is consuming. Alarm status The icon indicates that no alarm has been generated. The icon indicates that the device has a pre-alarm activated.
Page 31
CVM-B150-ITF-HF If an alarm has not been programmed for the parameter, the pre-alarm and alarm zones shown in the bar chart are calculated. Figure 26: Calculation of the bar chart� The calculation formulas are: Neutral-phase voltage and neutral voltage L = Primary rated voltage* 0.9...
CVM-B150-ITF-HF 4�5�- LED INDICATORS The CVM-B150 device features: - A CPU LED, which indicates that the device is working correctly with a 1 second flashing. A flashing of 0.5 seconds indicates that an error has occurred. - An ALARM LED, which indicates that an alarm has been activated with the LED flashing. If there is no alarm it remains switched off.
CVM-B150-ITF-HF 4�6�- INPUTS The CVM-B150 has two programmable digital inputs (terminals 7 and 8 in ) for working as: Figure 1 Logic input. Impulse input. Tariff selection. to configure the inputs. “5.6.17.- DIGITAL INPUTS.” and in you can see the status “5.1.7.- INTEGRATED FUNCTIONS.”...
CVM-B150-ITF-HF 5.- DISPLAY AND CONFIGURATION On the main screen, , you can access the various menus of the device: Figure 28 Figure 28:Main screen� > < > > < < Set Up Measure & View Billing Information closings Alarms >...
CVM-B150-ITF-HF 5�1�-MEASUREMENT DISPLAY MENU The screen in is the home screen for the measurement display menu. Figure 30 Figure 30: Main screen of the measurement display menu� The display options appear in the lower area: > < > > <...
CVM-B150-ITF-HF 5�1�1�- DISPLAY 1 PARAMETER� By selecting this option, you want to view a single parameter on the display. Figure 32: 1 parameter display screen� > > < < Default parameters Customize Main parameters menu Back > > < <...
Page 37
CVM-B150-ITF-HF 5�1�1�1�- Default parameters� This menu allows you to view the following types of parameters: Figure 34:Default parameters display screen (display 1 parameter)� > > < > < < Main Instantaneous menu parameters Incremental Back parameters Demand parameters > >...
Page 38
CVM-B150-ITF-HF 5�1�1�1�1�- Instantaneous parameters� On this screen, you can view all the parameters indicated in Figure 36, Table 9 Figure 36: Instantaneous parameters (display 1 parameter)� ph-n > > < < Display parameters Main varh Back menu > < Figure 37: Instantaneous parameters menu�...
Page 39
CVM-B150-ITF-HF For each of the instantaneous parameters you can view: The maximum and minimum value, with the date and time when it occurred. A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4.4.3.
Page 40
CVM-B150-ITF-HF 5�1�1�1�1�1�- Instantaneous parameters display menu� For each instantaneous parameter, this menu enables ( Figure 38 Figure 38:Instantaneous parameters, display menu (display 1 parameter)� Ph-n > > < > < < Main Graphic menu view Analog Back view View 4...
Page 41
CVM-B150-ITF-HF 5�1�1�1�1�1�1�- Graphic view shows the graphical display screen. Figure 40 Figure 40: Instantaneous parameters, graphic view (displays 1 parameter)� The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The lower area menu options are: 300s >...
Page 42
CVM-B150-ITF-HF 5�1�1�1�1�1�2�- Analog view� The analogue display screen is shown in Figure 42 Figure 42:Instantaneous parameters, analog view(display 1 parameter)� The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The lower area menu options are: >...
Page 43
CVM-B150-ITF-HF The alarm status: not activated, pre-alarm activated, alarm activated. icon flashes during the delay time in the alarm connection (ON) and disconnection (OFF). 5�1�1�1�2�- Incremental parameters� On this screen, , you can view all the parameters indicated in Figure 44 Table 10 Figure 44: Incremental parameters (display 1 parameter)�...
Page 44
CVM-B150-ITF-HF Table 10:Incremental parameters (display 1 parameter)� Display 1 parameter Icon Incremental parameters Active energy (2)(3)(4) Inductive reactive energy (2)(3)(4) Capacitive reactive energy (2)(3)(4) Total reactive energy (2)(3)(4) Apparent energy (2)(3)(4) Active tariff hours Emissions Cost There is a graphical representation for all these parameters on the screen,...
Page 45
CVM-B150-ITF-HF 5�1�1�1�2�1�- Incremental parameters display menu� For each incremental parameter, this menu enables the following: The value generated and consumed, The value for each tariff, T1, T2 and T3 and the total value of the 3 tariffs. The graphical representation of the parameter.
Page 46
CVM-B150-ITF-HF 5�1�1�1�2�1�1�- Tariff selection� The screen for selecting the tariff to be displayed is shown in Figure 50 Figure 49:Incremental parameters, tariff selection (display 1 parameter)� ∑ > > < < Tari Main varh Back menu > < Figure 50: Tariff selection menu�...
Page 47
CVM-B150-ITF-HF 5�1�1�1�2�1�2�- Graphic view The graphical representation of the energy closes is shown for all the incremental energy parameters, Figure 51 Figure 51:Incremental parameters, graphic view (displays 1 parameter)� > > < > < < Main Closes menu Previous Back Next >...
Page 48
CVM-B150-ITF-HF The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The device shows 59 energy closes for each display period. The energy close values are reset when the device is disconnected from the auxiliary power supply.
Page 49
CVM-B150-ITF-HF For each of the demand parameters you can view: The maximum and minimum value, with the date and time of the event. A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4.4.3.
Page 50
CVM-B150-ITF-HF 5�1�1�1�3�1�- Demand parameters display menu� For each demand parameter, this menu enables ( Figure 55 Graphical representation of the parameter. The analogue representation of the parameter. The value for each tariff, T1, T2 and T3. Figure 55:Demand parameters display menu (display 1 parameter)�...
Page 51
CVM-B150-ITF-HF 5�1�1�1�3�1�1�- Graphic view� shows the graphical display screen. Figure 57 Figure 57:Demand parameters, graphic view (displays 1 parameter)� 120m > > < < Integration time Main varh Back menu > < Figure 58: Graphic view menu� The integration time ( X-axis ) on the graph can be set to 120 minutes or 48 hours.
Page 52
CVM-B150-ITF-HF 5�1�1�1�3�1�2�- Analogue view� The analogue display screen is shown in Figure 59 Figure 59:Demand parameters, analog view (display 1 parameter)� > < Main varh Back menu > < Figure 60: Analog view menu� Use the keys to browse the different options.
Page 53
CVM-B150-ITF-HF icon flashes during the delay time in the alarm connection (ON) and disconnection (OFF). 5�1�1�1�3�1�3�- Tariff selection� The screen for selecting the tariff to be displayed is shown in Figure 61 Figure 61: Demand parameters, tariff selection (display 1 parameter)�...
Page 54
CVM-B150-ITF-HF 5�1�1�2�- Customise parameters On this screen, Figure 63, you can view the five custom screens with 1 parameter. Figure 63: Custom parameters screen (display 1 parameter)� > > < < Custom screens Main varh Back menu > < Figure 64: Custom parameters menu�...
Page 55
CVM-B150-ITF-HF 5�1�1�2�1�- Customisation screens shows the screen used to customise 1 parameter. Figure 65 These screens can also be configured for communications. See “6.- INTEGRATED COMMUNICATIONS”. Figure 65: Custom parameters screen (displays 1 parameter)� > > < < Parameter 1...
Page 56
CVM-B150-ITF-HF 5�1�1�2�1�1�- Parameter selection shows the screen for selecting the parameter for display. Figure 67 Figure 67: Custom parameters screen, parameter selection (displays 1 parameter)� > > > < < < Instantaneous Main parameters menu Incremental Back parameters Demand Delete...
Page 57
CVM-B150-ITF-HF 5�1�1�2�1�1�1�- Selecting an instantaneous parameter� shows the screen for selecting the Instantaneous parameters. Figure 69 Figure 69: Custom parameters screen, selecting an instantaneous parameter (displays 1 parameter)� ph-n > > < < Instantaneous parameters Main varh Back menu >...
Page 58
CVM-B150-ITF-HF Table 12: Instantaneous parameters that can be selected on the customisation screens� Customisation screen Icon Instantaneous parameter Icon Instantaneous parameter Phase-Neutral Voltage Capacitive reactive power Phase-Phase Voltage Total reactive power Current Apparent power Frequency Power factor Active power Cosine phi...
Page 59
CVM-B150-ITF-HF 5�1�1�2�1�1�2�- Selecting an incremental parameter� shows the screen for selecting an incremental parameter. Figure 71 Figure 71: Custom parameters screen, selecting an incremental parameter (displays 1 parameter)� > > < < Incremental parameters Main varh Back menu > <...
Page 60
CVM-B150-ITF-HF Table 13: Incremental parameters that can be selected on the customisation screens� Customisation screen Icon Incremental parameter Icon Incremental parameter Active energy Apparent energy Inductive reactive energy Active tariff hours Capacitive reactive energy Emissions Total reactive energy Cost To select a parameter, press the button to open the menu at the bottom for selecting the phase: ●...
Page 61
CVM-B150-ITF-HF 5�1�1�2�1�1�3�- Selecting a demand parameter� shows the screen for selecting a demand parameter. Figure 73 Figure 73: Custom parameters screen, selecting a demand parameter (displays 1 parameter)� > > < < Demand parameters Main varh Back menu > <...
Page 62
CVM-B150-ITF-HF Table 14: Demand parameters that can be selected on the customisation screens� Customisation screen Icon Demand parameter Current Active power Apparent power To select a parameter, press the button to open the menu at the bottom for selecting the phase:...
CVM-B150-ITF-HF 5�1�2�- DISPLAY 3 PARAMETERS� By selecting this option, you can view the three parameters at the same time on the display. Figure 75: 3 parameter display screen� The following options appear in the lower area: > > < <...
Page 64
CVM-B150-ITF-HF 5�1�2�1�- Default parameters� This menu allows you to view the following types of parameters: Figure 77:Default parameters display screen (display 3 parameters)� > > < > < < Main Instantaneous menu parameters Incremental Back parameters Demand parameters > >...
Page 65
CVM-B150-ITF-HF 5�1�2�1�1�- Instantaneous parameters� On this screen, you can view all the parameters indicated in Figure 79, Table 15� Figure 79: Instantaneous parameters (display 3 parameters)� ph-n > > < < Display parameters Main varh Back menu > < Figure 80: Instantaneous parameters menu�...
Page 66
CVM-B150-ITF-HF For each of the instantaneous parameters you can view: The maximum and minimum value, with the date and time when it occurred. A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4�4�3�...
Page 67
CVM-B150-ITF-HF 5�1�2�1�1�1�- Instantaneous parameters display menu� For each instantaneous parameter, this menu allows ( Figure 81 Figure 81: Instantaneous parameters, display menu (displays 3 parameters)� Ph-n > > < < Graphic view Main varh Back menu > < Figure 82: Instantaneous parameters menu�...
Page 68
CVM-B150-ITF-HF 5�1�2�1�1�1�1�- Graphic view� shows the graphical display screen. Figure 83 Figure 83: Instantaneous parameters, graphical representation (displays 3 parameters)� The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The lower area menu options are: 300s >...
Page 69
CVM-B150-ITF-HF 5�1�2�1�2�- Incremental parameters� On this screen, , you can view all the parameters indicated in Figure 85 Table 16 Figure 85: Incremental parameters (display 3 parameters)� > > < < Display parameters Main varh Back menu > < Figure 86: Incremental parameters menu�...
Page 70
CVM-B150-ITF-HF Table 16: Instantaneous parameters (display 3 parameters)� Display 3 parameters Icon Incremental parameters Active energy L1 (4) (5) Active energy L2 (4) (5) Active energy L3 (4) (5) Inductive reactive energy L1 (4) (5) Inductive reactive energy L2 (4) (5)
Page 71
CVM-B150-ITF-HF 5�1�2�1�2�1�- Incremental parameters display menu� For each incremental parameter ( ), you can view: Figure 87 The value generated and consumed, The value for each tariff, T1, T2 and T3 and the total value of the 3 tariffs. Graphical representation of the energy closes.
Page 72
CVM-B150-ITF-HF 5�1�2�1�2�1�1�- Tariff selection� The screen for selecting the tariff to be displayed is shown in Figure 89 Figure 89:Incremental parameters, tariff selection (display 3 parameters)� ∑ > > < < Tari Main varh Back menu > < Figure 90: Tariff selection menu�...
Page 73
CVM-B150-ITF-HF 5�1�2�1�2�1�2�- Graphic view� The graphical representation of the energy closes is shown for all the incremental energy parameters, Figure 91 Figure 91:Incremental parameters, graphic view (displays 3 parameters)� > > < > < < Main Closes menu Previous Back Next >...
Page 74
CVM-B150-ITF-HF The menu in the lower area disappears after 3 seconds. Press the key to display the lower area again. The device shows 59 energy closes for each display period. The energy close values are reset when the device is disconnected from the auxiliary power supply.
Page 75
CVM-B150-ITF-HF For each of the demand parameters you can view: The maximum value, with the date and time when it occurred. A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4.4.3.
Page 76
CVM-B150-ITF-HF 5�1�2�1�3�1�- Demand parameters display menu� For each demand parameter, you can view: The graphic view. The value for each tariff, T1, T2 and T3. Figure 95:Demand parameters, display menu (display 3 parameters)� > > < < Graphic view Tari...
Page 77
CVM-B150-ITF-HF 5�1�2�1�3�1�1�- Graphic view� shows the graphical display screen. Figure 97 Figure 97: Demand parameters, graphical representation (displays 3 parameters)� 120m > > < < Integration time Main varh Back menu > < Figure 98: Graphic view menu� The integration time (X-axis) on the graph can be set to 120 minutes or 48 hours.
Page 78
CVM-B150-ITF-HF 5�1�2�1�3�1�2�- Tariff selection� The screen for selecting the tariff to be displayed is shown in Figure 99 Figure 99:Demand parameters, tariff selection (display 3 parameters)� ∑ > > < < Tari Main varh Back menu > < Figure 100: tariff selection menu�...
Page 79
CVM-B150-ITF-HF 5�1�2�2�- Customise parameters On this screen, , you can view the five custom screens with 3 parameters. Figure 101 Figure 101: Custom parameters screen (display 3 parameter)� > > < < Custom screens Main varh Back menu > <...
Page 80
CVM-B150-ITF-HF 5�1�2�2�1�- Customisation screens shows the screen used to customise 3 parameters. Figure 105 These screens can also be configured for communications. See “6.- INTEGRATED COMMUNICATIONS” Figure 103: Custom parameters screen (displays 3 parameter)� > > < < Parameter selection...
CVM-B150-ITF-HF 5�1�3�- DISPLAY 4 PARAMETERS� By selecting this option, you can view the four parameters at the same time on the display. Figure 105: 4 parameter display screen� The following options appear in the lower area: > > < <...
Page 82
CVM-B150-ITF-HF 5�1�3�1�- Default parameters� This menu allows you to view the following types of parameters: Figure 107:Default parameters display screen (display 4 parameters)� > > < > < < Main Instantaneous menu parameters Incremental Back parameters Demand parameters > >...
Page 83
CVM-B150-ITF-HF 5�1�3�1�1�- Instantaneous parameters� On this screen, you can view all the parameters indicated in Figure 109, Table 18 Figure 109: Instantaneous parameters (display 4 parameters)� ph-n > > < < Display parameters Main varh Back menu > < Figure 110: Instantaneous parameters menu�...
Page 84
CVM-B150-ITF-HF A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4.4.3. CENTRAL AREA”� Table 18:Instantaneous parameters (display 4 parameters)� Display 4 parameters Display 4 parameters Icon Icon Instantaneous parameters Instantaneous parameters...
Page 85
CVM-B150-ITF-HF 5�1�3�1�1�1�- Instantaneous parameters display menu� For each instantaneous parameter, this menu allows ( Figure 111 Figure 111: Instantaneous parameters, display menu (display 4 parameters)� Ph-n > > < < Graphic view Main varh Back menu > < Figure 112: Instantaneous parameters menu�...
Page 86
CVM-B150-ITF-HF 5�1�3�1�1�1�1�- Graphic view� shows the graphical display screen. Figure 113 Figure 113: Instantaneous parameters, graphical representation (displays 4 parameters)� The menu in the lower area disappears after a few seconds. Press the key to display the lower area again.
Page 87
CVM-B150-ITF-HF 5�1�3�1�2�- Incremental parameters� On this screen, , you can view all the parameters indicated in Figure 115 Table 19 Figure 115: Incremental parameters (display 4 parameters)� > > < < Display parameters Main varh Back menu > < Figure 116: Incremental parameters menu�...
Page 88
CVM-B150-ITF-HF Table 19:Incremental parameters (display 4 parameters)� Display 4 parameters Icon Incremental parameters Active energy L1 (8) (9) Active energy L2 (8) (9) Active energy L3 (8) (9) Active energy III (8) (9) Inductive reactive energy L1 (8) (9) Inductive reactive energy L2...
Page 89
CVM-B150-ITF-HF 5�1�3�1�2�1�- Incremental parameters display menu� For each incremental parameter, this menu enables the following ( Figure 117 The value generated and consumed. The value for each tariff, T1, T2 and T3 and the total value of the 3 tariffs.
Page 90
CVM-B150-ITF-HF 5�1�3�1�2�1�1�- Tariff selection� The screen for selecting the tariff to be displayed is shown in Figure 119 Figure 119:Incremental parameters, tariff selection (display 4 parameters)� ∑ > > < < Tari Main varh Back menu > < Figure 120: Tariff selection menu�...
Page 91
CVM-B150-ITF-HF 5�1�3�1�2�1�2�- Graphic view� The graphical representation of the energy closes is shown for all the incremental energy parameters, Figure 121 Figure 121: Incremental parameters, graphic view (displays 4 parameters)� > > < > < < Main Closes menu Previous...
Page 92
CVM-B150-ITF-HF The energy close values are reset when the device is disconnected from the auxiliary power supply. 5�1�3�1�3�- Demand parameters� , you can view all the maximum demand parameters indicated in Table 20. On this screen, Figure 123 Figure 123:Demand parameters (display 4 parameters)�...
Page 93
CVM-B150-ITF-HF A bar chart with the indications of the instantaneous value, maximum and minimum values and alarms, see “4�4�3� CENTRAL AREA”� Table 20:Demand parameters (display 4 parameters)� Display 4 parameters Icon Demand parameters Current L1 Current L2 Current L3...
Page 94
CVM-B150-ITF-HF 5�1�3�1�3�1�- Demand parameters display menu� For each demand parameter, you can view: The graphic view. The value for each tariff, T1, T2 and T3. Figure 125: Demand parameters, display menu (display 4 parameters)� > > < < Graphic view...
Page 95
CVM-B150-ITF-HF 5�1�3�1�3�1�1�- Graphic view� shows the graphical display screen. Figure 127 Figure 127: Demand parameters, graphic view (displays 4 parameters)� 120m > > < < Integration time Main varh Back menu > < Figure 128:Graphic view menu� The integration time (X-axis) on the graph, can be set to 120 minutes or 48 hours.
Page 96
CVM-B150-ITF-HF 5�1�3�1�3�1�2�- Tariff selection� The screen for selecting the tariff to be displayed is shown in Figure 129 Figure 129:Demand parameters, tariff selection (display 4 parameters)� ∑ > > < < Tari Main varh Back menu > < Figure 130: tariff selection menu�...
Page 97
CVM-B150-ITF-HF 5�1�3�2�- Customise parameters On this screen, , you can view the five custom screens with 4 parameters. Figure 131 Figure 131: Custom parameters screen (display 4 parameter)� > > < < Custom screens Main varh Back menu > <...
Page 98
CVM-B150-ITF-HF 5�1�3�2�1�- Customisation screens shows the screen used to customise 4 parameters. Figure 133 These screens can also be configured for communications. See “6.- INTEGRATED COMMUNICATIONS” Figure 133: Custom parameters screen (displays 4 parameter)� > > < < Parameter selection...
CVM-B150-ITF-HF 5�1�4�- INTEGRATED FUNCTIONS� On this screen, , you can view the status of the digital inputs integrated in the device. Figure 135 Figure 135: Display screen of digital inputs integrated in the device� > < Main varh Back menu >...
CVM-B150-ITF-HF 5�1�5�- EXPANSION MODULES� Note: This option only appears when the device is connected to an expansion module of Transistor Digital Inputs/Outputs (M-CVM-AB-8I-8OTR), Relay Digital Inputs/Outputs (M-CVM-AB-8I-8OR) or Analogue Inputs/Outputs (M-CVM-AB-4AI-8AO). On the main screen, , of this option, select the expansion module for which you want to Figure 137 display the status of the inputs.
Page 101
CVM-B150-ITF-HF Figure 139: Display screen of digital inputs of an expansion module� > > < < Next Main Previous menu > Back > < < Figure 140: Display menu of an expansion module� Use the keys to select the different options.
CVM-B150-ITF-HF 5�2�- ENERGY CLOSES MENU The screen in is the home screen for the energy close menu. Figure 141 Figure 141: Main screen of the energy closes menu� Energy closes menu: > > < < Active Energy Total Main varh...
CVM-B150-ITF-HF 5�2�1�- ACTIVE ENERGY CLOSES III OF THE TOTAL TARIFF AND OF REACTIVE ENERGY III OF THE TOTAL TARIFF� This screen displays the graphical representation of the closes of consumed active energy III of the total tariff (the sum of the three tariffs) after selecting the option.
Page 104
CVM-B150-ITF-HF The menu in the lower area disappears after a few seconds. Press the key to display the lower area again. The device shows 29 energy closes for each display period. When a given close is selected the display shows: The value of the selected energy close.
CVM-B150-ITF-HF 5�3�- ALARM MENU The screen in is the alarm display menu screen. Where all the alarms programmed in the Figure 145 device and in the connected expansion modules are displayed, indicating a brief description and the date and time of the alarm activation.
Page 106
CVM-B150-ITF-HF If no key is pressed for 5 minutes, the display screen changes automatically to the default screen. Figure 147: Alarm menu description table� The programmed alarms description table, , is made up of 4 columns: Figure 147 Cd� : Indicates the code of the variable that controls the programmed alarm, Table 21 Description : Description of alarm that you have programmed.
CVM-B150-ITF-HF 5�4�- LOG MENU The screen in is the home screen of the menu log, which shows the log of the alarms and Figure 148 events that have occurred in the device. Figure 148: Main screen log menu� The log menu can show: >...
CVM-B150-ITF-HF 5�4�1�- ALARM LOG This screen shows the log of the last 50 alarms occurring in the device and installed expansion modules, including a brief description and the date and time of the last alarm activation. Figure 150:Alarm log >...
Page 109
CVM-B150-ITF-HF Figure 152: Details of the alarm log� The alarm log, , has 4 columns: Figure 152 Cd� : indicates the code of the alarm that occurred (in hexadecimal) Description: Description of the alarm. Example: Alarm M0_S3 act with latch M0, Indicates the module where the alarm was activated: M0, is an alarm triggered in the device.
CVM-B150-ITF-HF 5�4�2�- EVENT LOG This screen shows the log of the last 50 events occurring in the device and the installed expansion modules, including a brief description and the date and time of the event. Figure 153:Event log� > >...
CVM-B150-ITF-HF 5�5�- INFORMATION MENU The screen in , is the home screen of the information menu. Figure 155 Figure 155: Main screen of information menu� In the information menu you can view: > > < > < < Main System...
CVM-B150-ITF-HF 5�5�1�- SYSTEM INFORMATION� On the system information screen, , you will view the model, serial number and firmware Figure 157 version of the device. Figure 157: System information screen� > < Main varh Back menu > < Figure 158: System information menu�...
CVM-B150-ITF-HF 5�5�2�- INTEGRATED FUNCTIONS� On the integrated functions screen, , you will view the configuration of the communications Figure 159 and digital inputs and outputs. Figure 159: Integrated functions screen� > > < > < < Main Communications 1 menu...
CVM-B150-ITF-HF 5�5�3�- EXPANSION MODULES� On the expansion modules screen, , you will view the model, serial number and firmware Figure 161 version of each of the expansion modules. Figure 161: Expansion modules information screen� > > < > < <...
Page 115
CVM-B150-ITF-HF 5�5�3�1�- Expansion modules of Transistor and Relay digital inputs/outputs The screen in , is one of the information display screens for the expansion module. Figure 163 Figure 163: Digital inputs information screen (Transistor Digital Inputs/Outputs Module)� This screen displays the configuration of the digital inputs of the module.
Page 116
CVM-B150-ITF-HF When selecting the digital outputs option, , you will view the screen in , with the Figure 165 configuration information for the digital outputs. Figure 165: Digital outputs information screen (Transistor Digital Inputs/Outputs Module) 5�5�3�2�- Analogue Inputs/Outputs expansion modules The screen in , is one of the information display screens for the expansion module.
Page 117
CVM-B150-ITF-HF > > < < Analog Inputs Main Analog menu Outputs Back > > < < Figure 167: Analogue Inputs/Outputs Module menu� Use the keys to select the different options. If no key is pressed for 5 minutes, the display screen changes automatically to the default screen.
Page 118
CVM-B150-ITF-HF 5�5�3�3�- Modbus TCP (Bridge) communications expansion modules The screen in , is a screen that displays the information of the Modbus TCP communications Figure 169 module. Figure 169: Information screen of the Modbus TCP ( Bridge ) module (TCP communications)�...
Page 119
CVM-B150-ITF-HF On selecting the RS-485 option, , the screen in , appears with information on the Figure 171 configuration of the RS-485 gateway. Figure 171: Information screen of the Modbus/TCP ( Bridge) module (RS-485 Gateway)� 5�5�3�4�- LonWorks communications expansion modules...
Page 120
CVM-B150-ITF-HF > < Main varh Back menu > < Figure 173: LonWorks module menu� Use the keys to select the different options. To confirm the selection, press the key If no key is pressed for 5 minutes, the display screen changes automatically to the default screen.
Page 121
CVM-B150-ITF-HF > < Main varh Back menu > < Figure 175: Profibus module menu� Use the keys to select the different options. To confirm the selection, press the key If no key is pressed for 5 minutes, the display screen changes automatically to the default screen.
Page 122
CVM-B150-ITF-HF > < Main varh Back menu > < Figure 177: MBus module menu� Use the keys to select the different options. To confirm the selection, press the key If no key is pressed for 5 minutes, the display screen changes automatically to the default screen.
Page 123
CVM-B150-ITF-HF > > < < Main Port menu > Back > < < Figure 179: Datalogger module menu� Use the keys to select the different options. If no key is pressed for 5 minutes, the display screen changes automatically to the default screen.
Page 124
CVM-B150-ITF-HF 5�5�3�8�- Modbus TCP (Switch) communications expansion modules The screen in , is a screen that displays the information of the Modbus TCP (Switch) Figure 181 communications module. Figure 181: Information screen of the Modbus TCP ( Switch ) module (TCP communications)�...
CVM-B150-ITF-HF 5�5�4�- CIRCUTOR S�A�U� , shows all the Circutor contact information. This screen, Figure 183 Figure 183: Circutor screen� > < Main varh Back menu > < Figure 184: Circutor menu� Use the keys to browse the various menus. To access the selected menu press the key If no key is pressed for 5 minutes, the display screen changes automatically to the default screen.
CVM-B150-ITF-HF 5�6�- SETUP MENU If the setup menu is protected by an access password there is an icon on the main menu screen, Figure 185 Figure 185:Protected setup menu� screen will appear when accessing menu enter access password ). Password enablement is selected in section Figure 186 “5.6.4.
Page 127
CVM-B150-ITF-HF > > < > < < Main menu Con guration values Con rm Previous and save Next > > < < Figure 187: Access password menu� Use the keys to select the different options. To confirm the selection, press the key If no key is pressed for 5 minutes, the display screen changes automatically to the default screen.
CVM-B150-ITF-HF 5�6�1�- DATE AND TIME� The current date and time are selected on this screen, Figure 190 Figure 190: Date and time configuration screen� The digit selected is indicated in white. > > < > < < Main menu Con guration...
CVM-B150-ITF-HF 5�6�2�- TIME ZONE� The time zone is selected on this screen Figure 192 Figure 192: Time zone configuration screen� > > < > < < Main menu Con guration values Back Previous Con rm and save Next > >...
CVM-B150-ITF-HF 5�6�3�- LANGUAGE� The device language is selected on this screen Figure 194 Figure 194: Device language configuration screen� > > < < Con guration values Main Con rm menu and save > Back > < < Figure 195: Setup menu : Language�...
CVM-B150-ITF-HF 5�6�4�- ACCESS KEY� The access key to the device setup menu is selected on this screen Figure 196 Figure 196: Access key configuration screen� The digit selected is indicated in white. > > < > < < Main menu...
CVM-B150-ITF-HF Use the keys to select the different options. To confirm the selection, press the key 5�6�5�- MEASUREMENT CONNECTION MODE� This screen, , is for selecting the measurement connection mode. Figure 198 Figure 198: Measurement connection mode configuration screen� >...
CVM-B150-ITF-HF To confirm the selection, press the key 5�6�6�- RATIO OF VOLTAGE TRANSFORMERS� The voltage transformer ratio is selected on this screen, Figure 200 Figure 200: Voltage transformer ratio configuration screen� The parameter selected is indicated in white. > >...
CVM-B150-ITF-HF Secondary voltage: Maximum value: 999,9 Minimum value: 10. Rated Phase-Neutral Voltage: Maximum value: (Rated Phase-Neutral Voltage / Voltage Ratio) ≤ 1000 Minimum value: (Rated Phase-Neutral Voltage / Voltage Ratio) ≥ 50 Maximum possible voltage ratio: 9999. Note: The voltage ratio is the ratio between the primary and secondary voltage.
Page 136
CVM-B150-ITF-HF > > > < < > < < Con guration Previous Main values menu Next Back Con rm Delete Delete and save parameter character > > < < > > < < Figure 203: Setup menu : Current transformer ratio�...
CVM-B150-ITF-HF 5�6�8�- INSTALLATION DATA� The following installation features are selected on this screen Figure 204 Number of quadrants. Figure 204: Installation features configuration screen� The parameter selected is indicated in white. > > < < Con guration values Main...
CVM-B150-ITF-HF 5�6�9�- DEMAND� The maximum demand configuration parameters are selected on this screen Figure 206 The type of integration of the demand. The integration time in minutes. Figure 206: The maximum demand parameters configuration screen� The parameter selected is indicated in white.
CVM-B150-ITF-HF ● When programming the integration time: Maximum value: 60 minutes. Minimum value: 1 minute. Use the keys to select the different options. To confirm the selection, press the key 5�6�10�- ENERGY CONSUMPTION COSTS� The energy consumption costs are selected on this screen Figure 208 ...
CVM-B150-ITF-HF Use the keys to select the different options. To confirm the selection, press the key Cost of the tariffs: Maximum value: 100.000 Minimum value: 0.00000 5�6�11�- ENERGY GENERATION COSTS� The energy generation costs are selected on this screen Figure 210 ...
CVM-B150-ITF-HF Use the keys to select the different options. To confirm the selection, press the key Cost of the tariffs: Maximum value: 100.000 Minimum value: 0.00000 5�6�12�- CONSUMPTION EMISSIONS� The carbon consumption emission ratios are selected on this screen Figure 212 The carbon emissions ratio is the amount of emissions released into the atmosphere to produce a unit of electricity (1 kWh).
CVM-B150-ITF-HF > > > < < > < < Con guration Previous Main values menu Next Back Con rm Delete Delete and save parameter character > > < < > > < < Figure 213: Setup menu: The C02 consumption emissions Use the keys to select the different options.
Page 143
CVM-B150-ITF-HF Figure 214: The C0 generation emissions configuration screen� The parameter selected is indicated in white. > > > < < > < < Con guration Previous Main values menu Next Back Con rm Delete Delete and save parameter character >...
CVM-B150-ITF-HF 5�6�14�- RELAY DIGITAL OUTPUTS� Select the output to configure on the main configuration screen of the relay digital outputs, Figure Figure 216: Main configuration screen of relay digital outputs� > > < < Output 1 Main Output 2 menu >...
Page 145
CVM-B150-ITF-HF After selecting the output to configure, , the following parameters can be configured: Figure 218 The variable code that controls the relay. The Pre-alarm value. The minimum value below which the relay is activated. The maximum value above which the relay is activated.
Page 146
CVM-B150-ITF-HF ● When programming the variable code which controls the relay digital output, you need the Table 21 Note: To cancel the operation of a digital output, the 0 code must be programmed. Table 21: Code of variables for programming the digital outputs and transistor�...
Page 147
CVM-B150-ITF-HF Table 21 (Continuation): Code of variables for programming the digital outputs and transistor� Variable Total Reactive Energy Generated (13) Total Total Total Total Total Reactive Energy Consumed (13) Total Total Total Total Apparent Energy Generated (13) Total Total Total...
Page 148
CVM-B150-ITF-HF Table 21 (Continuation): Code of variables for programming the digital outputs and transistor� Variable Analogue input I3 Analogue input I4 The integrated variables are those that the device has as standard. (10) If in the device there is more than one module connected with the same type of inputs, the module with the lowest (11) number is the one with the lowest serial number.
Page 149
CVM-B150-ITF-HF Table 22(Continuation):Units and maximum and minimum values of the programming variables of the digital outputs� Variable Units Maximum Minimum Maximum Demand of Active power 180000 Maximum Demand of Apparent Power The voltage ratio is the ratio between the primary and secondary voltage.
CVM-B150-ITF-HF 5�6�15�- TRANSISTOR DIGITAL OUTPUTS� Select the output to configure on the main configuration screen of the transistor digital outputs, Figure Figure 220: Main configuration screen of transistor digital outputs� > > < < Output 1 Main Output 2 menu >...
Page 151
CVM-B150-ITF-HF After selecting the output to configure, you can configure the transistor output mode, Alarm or Impulse output, and the parameters for each mode. Alarm, to select the alarm mode of the transistor digital output. Impulses, to select the impulse mode of the transistor digital output.
Page 152
CVM-B150-ITF-HF > > > < < > < < Con guration Previous Main values menu Next Back Con rm Delete Delete and save parameter character > > < < > > < < Figure 223: Setup menu: transistor digital outputs (alarm mode)�...
Page 153
CVM-B150-ITF-HF ● When programming the latch: Enable the latch, Disable the latch. The latch is selected in this parameter, i.e., the transistor digital output will be locked after it has been tripped, even when the condition that triggered it has disappeared.
Page 154
CVM-B150-ITF-HF PE: Pulse energy in Wh (Energy meter factor) TP : low period + high period, in seconds. For example: If the installation can consume 100kW, a suitable configuration could be pulses of 10W ( Energy meter factor) with a high and low period of 50 ms.
CVM-B150-ITF-HF Maximum value: 65536. Minimum value: 1. 5�6�16�- DIGITAL INPUTS� The operating mode for digital inputs and the parameters for each mode are selected in the main con- figuration screen for digital inputs, Figure 226 Figure 226: Main configuration screen for digital inputs�...
Page 156
CVM-B150-ITF-HF Logic state, to select the inputs as a logic input. The configuration parameters of digital inputs 1 and 2 change according to the operating modes. 5�6�16�1�- Configuration of digital inputs, Tariff mode� When selecting the tariff mode the two inputs operate in the same mode; they cannot be programmed...
Page 157
CVM-B150-ITF-HF Figure 229: Digital inputs configuration screen (impulse mode)� The parameter selected is indicated in white. > > > < < > < < Con guration Previous Main values menu Next Back Con rm Delete Delete and save parameter character >...
Page 158
CVM-B150-ITF-HF ● When programming the meter factor: The energy meter factor is the number of times the value of the digital input will be increased for each impulse detected by said input. 5�6�16�3�- Configuration of digital inputs, logic state mode�...
CVM-B150-ITF-HF > > < > < < Main Con guration menu values Back Previous Con rm and save Next > > < < > < Figure 232: Setup menu: Digital inputs (logic state mode)� ● The configuration values are: Positive, the digital input logic is positive �...
Page 160
CVM-B150-ITF-HF 5�6�17�1�- Configuration parameters, Modbus protocol� When selecting the Modbus communications protocol, , you can program the following Figure 233 parameters: The peripheral number. The transmission speed, Baud Rate. The parity. The number of stop bits. ...
Page 161
CVM-B150-ITF-HF ● When programming the ID: The ID is the peripheral number assigned to the device in the Modbus network. Maximum value: 255. Minimum value: 0. ● When programming the transmission speed, Baud rate, the configuration values are: The possible transmission speeds: 9600, 19200, 38400, 57600, 76800 or 115200�...
CVM-B150-ITF-HF > > > < < > < < Con guration Previous Main values menu Next Back Con rm Delete Delete and save parameter character > > < < > > < < Figure 236: Setup menu: BACnet protocol� ● When programming the transmission speed, Baud Rat, the configuration values...
Page 163
CVM-B150-ITF-HF Figure 237: Parameter reset screen� > > < > < < Main menu Con guration values Previous Back Con rm Next and save > > < < > < Figure 238:Setup menu: Parameter reset� ● The configuration values are: Enable reset, enable reset of selected parameter.
CVM-B150-ITF-HF 5�6�19�- USER INTERFACE Select the time to off back for the display, keyboard sensitivity, display decimal and date format on the user interface screen, Figure 239 Figure 239:User interface screen� > > > < < > < < Con guration...
CVM-B150-ITF-HF ● When programming the sensitivity of the keyboard, the configuration values are: Low, Normal, High. ● When programming the display decimal, the configuration values are: Coma, Point. ● When programming the date format, the configuration values are: Format dd/mm/yyyy, Format dd/mm/yyyy.
CVM-B150-ITF-HF 6.- INTEGRATED COMMUNICATIONS The CVM-B150 devices have one RS-485 communications port. The device has as standard two communications protocols: MODBUS RTU ® and BACnet. The protocol and configuration parameters are selected on the setup menu. ( “5.6.18.- INTEGRATED COMMUNICATIONS.”...
CVM-B150-ITF-HF 6�2�- MODBUS PROTOCOL The MODBUS protocol is a communication standard in the industry that enables the network connection of multiple devices, where there is a master and multiple slaves. It allows individual master- slave dialogue and also enables commands in broadcast format.
CVM-B150-ITF-HF 6�2�1�- EXAMPLE OF MODBUS QUERY Query: Instantaneous value of the L1 phase voltage Initial No� of Address Function register registers 0000 0002 70B0 Address: 0A, Peripheral number: 10 in decimal. Function: 04, Read function. Initial Register: 0000, register from which to start reading.
Page 169
CVM-B150-ITF-HF Table 24: Modbus memory map: measurement variables Parameter Symbol Instantaneous Maximum Minimum (18) Units Phase voltage L1 00-01 100-103 300-303 157C Current L1 02-03 104-107 304-307 157D Active Power L1 04-05 108-10B 308-30B 1580 Inductive Reactive Power L1 kvarL1...
CVM-B150-ITF-HF 6�3�4�- COST VARIABLES These parameters occupy 2 registers each. Each unit occupies a separate register. For these variables Function 0x04 is implemented: reading registers. Table 27: Modbus memory map: cost variables Tariff 1 Tariff 2 Tariff 3 Total Parameter...
Page 176
CVM-B150-ITF-HF 6�3�6�1�- Date and time These parameters occupy 1 register each. Table 29:Modbus memory map: Configuration variables (Date and Time)� Date and Time Configuration variable Address Valid data window Default value 2013 to 2076 Year 283C Month 283D 1 to 12...
Page 177
CVM-B150-ITF-HF 6�3�6�3�- Language This parameter occupies 1 register. Table 32:Modbus memory map: Configuration variables (language)� Language Configuration variable Address Valid data window Default value 0: Spanish 1: English 2: German 3: French Device language 2A9C 4: Chinese 5: Korean 6: Norwegian 7: Catalan 6�3�7�4�- Access key...
Page 178
CVM-B150-ITF-HF 6�3�6�6�- Ratio of voltage and current transformers These parameters occupy 2 registers each. Table 35:Modbus memory map: Configuration variables (transformation ratios) Transformation ratios Configuration variable Address Valid data window Default value 1 - 500000 Primary voltage 2710-2711 (21) (22)
Page 179
CVM-B150-ITF-HF 6�3�6�9�- Cost of energy consumption and generation The Cost configuration variables occupy 2 registers each. The Currency configuration variables occupy 4 registers. Table 38:Modbus memory map: Configuration variables (Energy cost) Energy cost Configuration variable Address Valid data window Default value...
Page 180
CVM-B150-ITF-HF 6�3�6�11�- Relay digital outputs The Maximum Value and Minimum Value configuration variables occupy 2 registers each. All other variables occupy 1 register each. Table 40:Modbus memory map: Relay digital outputs� Configuration of the digital outputs of the relay Address...
Page 181
CVM-B150-ITF-HF Variables with 2 decimals. (32) 6�3�6�12�- Transistor digital outputs The Maximum Value and Minimum Value configuration variables occupy 2 registers each. All other variables occupy 1 register each. Table 42: Modbus memory map: Configuration variables (Transistor digital outputs)� Configuration of Transistor Digital Outputs...
Page 182
CVM-B150-ITF-HF When programming a value of more than 1, programme the impulse operating mode and energy meter factor for this (35) mode simultaneously. the characters must be sent in hexadecimal. (36) Note: The 11 registers must be written and read at once (as a group), otherwise it will respond with an error.
Page 183
CVM-B150-ITF-HF 6�3�6�16�- Position of input channels This parameter occupies 1 register. Table 46:Modbus memory map: Configuration variables (Position of input channels)� Position of input channels Configuration variable Address Default value Position of input channels 2850 0x0924 This variable allows you to switch the voltage and current channels and reverse the current direction, enabling the correction of an incorrect installation.
Page 184
CVM-B150-ITF-HF Response: Address Function No� of Bytes Register 0924 XXXX Address: 0A, Responding peripheral number: 10 in decimal. Function: 04, Read function. No� of bytes: 02, No. of bytes received. Register: 0924 (0000100100100100bin) Indicates: - (0000100100100100bin) The direction of the currents does not change,...
Page 185
CVM-B150-ITF-HF Table 50:Modbus memory map: Configuration variables (Configuration of the parameter customisation screens)� Configuration of the parameter customisation screens Valid data Configuration variable Address margin 3 parameter screens Screen 1 Screen 2 Screen 3 Screen 4 Screen 5 Parameter 1: Variable...
Page 186
CVM-B150-ITF-HF Table 51 (Continuation): Modbus memory map: Configuration variables (Configuration of the parameter customisation screens) Configuration of the parameter customisation screens Valid data Configuration variable Address margin Parameter 4: 0: Consumption (39) 2A3B 2A4B 2A5B 2A6B 2A7B Consumption or Generation...
CVM-B150-ITF-HF Table 54:Configuration of custom screens: Tariffs Tariffs Parameter (40) Tariff Value Tariff Value Tariff 1 0x0000 Tariff 3 0x0002 Tariff 2 0x0001 Total value of 3 tariffs 0x0003 (40) If the variable has no tariff option, 00 will be sent.
Page 188
CVM-B150-ITF-HF 6�3�7�3�- Internal temperature These parameters occupy 2 registers. Table 58:Modbus memory map: Internal temperature� Internal temperature (44) Configuration variable Address Valid data window Internal temperature 2852-2853 ºC with 2 decimals For this variable only Function 0x04 is implemented: reading registers.
Page 189
CVM-B150-ITF-HF Table 60 (Continuation): Modbus memory map: Alarm status: Relay digital outputs� Alarm status Relay digital outputs Address Configuration variable Valid data window Output 1 Output 2 0: No alarm, Status 7564 7578 (47) 1: Active alarm 0: No alarm,...
CVM-B150-ITF-HF 6�3�8�- DELETING PARAMETERS These parameters occupy 1 register each. Parameters can be deleted using Function 0x05: writing a relay. Table 63:Modbus memory map: Deleting parameters Deleting parameters Address Value to be sent System reset 07D0 0x00FF Deleting energies 0834...
CVM-B150-ITF-HF a) #Baud x – where x can be: 9600, 19200, 38400, 57600, 76800, 115200 b) #MAC x – where x can be: 0 ... 127 c) #ID x – where x can be: 0 ... 4194303 For further information on the protocol: www.bacnet.org 6�5�- PICS MAP...
Page 193
CVM-B150-ITF-HF DESCRIPTION SYMBOL ID OBJECTS OBJECT NAME UnitS Potencia reactiva Reactive power kvar 1 ReactPwrPh1 kvar Factor de potencia Power factor PF 1 PwrFactPh1 Tensión fase-neutro Voltage phase to neutral Ph2NU2 Corriente Current Ph2Current Potencia activa Active power kW 2...
Page 194
CVM-B150-ITF-HF DESCRIPTION SYMBOL ID OBJECTS OBJECT NAME UnitS Potencia aparente L1 Aparent power L1 AI40 AppPwrPh1 Potencia aparente L2 Aparent power L2 AI41 AppPwrPh2 Potencia aparente L3 Aparent power L3 AI42 AppPwrPh3 Potencia aparente Three phase aparent kVAIII AI43 AppPw3Ph trifásica...
CVM-B150-ITF-HF 7.- EXPANSION MODULES The device has following expansion modules that can be connected to it. The modules are: Transistor Digital Inputs/Outputs (M-CVM-AB-8I-8OTR), Relay Digital Inputs/Outputs (M-CVM-AB-8I-8OR) Analogue Inputs/Outputs (M-CVM-AB-4AI-8AO) Modbus TCP Bridge communications module (M-CVM-AB-Modbus-TCP(Bridge)) ...
Page 196
CVM-B150-ITF-HF To install, firstly remove the protective cover of the expansion connector located at the rear of the device. To do so: a�- Remove the two fastening pins that secure the protective cover with a flat tip screwdriver, Figure Protective cover Figure 242: Remove the two fastening pins�...
Page 197
CVM-B150-ITF-HF and secure it by inserting the 4 fastening pins into the corresponding slots, Figure 245: Insert the fastening pins into the corresponding slots� Instruction Manual...
CVM-B150-ITF-HF 7�2�- RELAY DIGITAL INPUTS/OUTPUTS This expansion module features 8 relay digital inputs and 8 relay digital outputs. 7�2�1�- CONNECTION TERMINALS A�- Terminals on the upper face Table 64: List of terminals on the upper face, Relay digital inputs/outputs module�...
CVM-B150-ITF-HF 7�2�2�- CONNECTION DIAGRAMS A�- Relay digital outputs Relay 1 2 3 4 5 6 7 8 9 10 External power Figure 248: Connection diagram, relay digital outputs� B�- Digital inputs 12 V DC COMM Free voltage input Figure 249: Connection diagram, digital inputs�...
CVM-B150-ITF-HF 7�2�3�- CONFIGURATION Access the configuration menu, as described in , and enter the configuration icon “5.6.- SETUP MENU” of the expansion modules, The main screen of the expansion modules is shown in Figure 250 Figure 250: Main screen of expansion modules�...
Page 201
CVM-B150-ITF-HF The following options appear in the lower area: > > < < Digital input Digital Main Relay menu outputs > Back > < < Figure 252: Setup menu : relay digital inputs/outputs� Use the keys to select the different options.
Page 202
CVM-B150-ITF-HF Figure 253: Main configuration screen for relay digital inputs� > > < > < < Main Mode menu Back Impulsos Digital inputs 1...8 > > < < Figure 254: Setup menu: digital inputs� Use the keys to select the different options.
Page 203
CVM-B150-ITF-HF Configuration of digital inputs, impulse mode.” 7�2�3�1�2�- Configuration of a digital input, logic state mode� When selecting the configuration of digital inputs in logic state mode, you can program the input logic as positive or negative. The configuration of a digital input in logic state mode in the expansion modules is the same as the configuration of the digital inputs in logic state mode integrated in the device, see “5.6.17.3.-...
CVM-B150-ITF-HF To confirm the selection, press the key After selecting the output to configure, you can configure the following parameters: The variable code that controls the relay. The pre-alarm value. The minimum value below which the relay is activated.
Page 205
CVM-B150-ITF-HF Table 67: Modbus memory map: Relay digital outputs, expansion modules (Table 2)� Configuration of relay digital outputs: Slot 1 Address Configuration variable Output Output Output Output Output Output Output Output Maximum value C350 C364 C378 C38C C3A0 C3B4 C3C8...
Page 206
CVM-B150-ITF-HF Table 69:Modbus memory map: Relay digital outputs, expansion modules (Table 4)� Configuration of the relay digital outputs: Slot 3 Address Configuration variable Output Output Output Output Output Output Output Output Maximum value CB20 CB34 CB48 CB5C CB70 CB84 CB98...
Page 207
CVM-B150-ITF-HF Table 71: Modbus memory map: Manual programming of outputs, expansion modules (Table 1)� Manual programming of relay digital outputs Configuration variable Valid data window Default value 0: Automatic Programming status (53) 1:Manual 0: Open Value 1:Closed When programming the Programming status manually set the output for the relays manually, using the Value parameter.
Page 208
CVM-B150-ITF-HF 7�2�4�3�- Programming the digital inputs The Modbus memory map for the digital inputs of the relay digital inputs/outputs module is the same as the transistor digital inputs/outputs module, see “7.3.4.3.- Programming the digital inputs” 7�2�4�4�- Status of digital inputs...
Page 209
CVM-B150-ITF-HF Table 77: Modbus memory map: Status of relay digital outputs (Table 2)� Status of relay digital outputs: Slot 1 Address Configuration variable Output Output Output Output Output Output Output Output Latch C670 C684 C698 C6AC C6C0 C6D4 C6E8 C6FC...
Page 210
CVM-B150-ITF-HF Table 79: Modbus memory map: Status of relay digital outputs (Table 4)� Status of relay digital outputs: Slot 3 Address Configuration variable Output Output Output Output Output Output Output Output Latch CE40 CE54 CE68 CE7C CE90 CEA4 CEB8 CECC...
CVM-B150-ITF-HF 7�3�- TRANSISTOR DIGITAL INPUTS/OUTPUTS This expansion module contains 8 transistor digital inputs and 8 transistor digital outputs. 7�3�1�- CONNECTION TERMINALS A�- Terminals on the upper face Table 81:List of terminals on the upper face, Transistor digital inputs/outputs module� Device terminals...
CVM-B150-ITF-HF 7�3�2�- CONNECTION DIAGRAMS A�- Transistor digital outputs Optocoupler 1 2 3 4 5 6 7 8 9 10 External power Figure 259:Connection diagram, transistor digital outputs� B�- Digital inputs 12 V DC COMM Free voltage input Figure 260:Connection diagram, digital inputs�...
CVM-B150-ITF-HF 7�3�3�- CONFIGURATION Access the configuration menu, as described in , and enter the configuration icon “5.6.- SETUP MENU” of the expansion modules, The main screen of the expansion modules is shown in Figure 261 Figure 261: Main screen of expansion modules�...
Page 214
CVM-B150-ITF-HF > > < < Digital inputs Digital Main Transistor menu outputs > Back > < < Figure 263: Setup menu : transistor digital inputs/outputs� Use the keys to select the different options. To confirm the selection, press the key 7�3�3�1�-...
CVM-B150-ITF-HF The following options appear in the lower area: > > < < Output 1...8 Main varh Back menu > < Figure 265: Setup menu : transistor digital outputs Use the keys to select the different options. To confirm the selection, press the key...
Page 216
CVM-B150-ITF-HF Table 83: Modbus memory map: Transistor digital outputs, expansion modules (Table 1)� Configuration of Transistor Digital Outputs Default Configuration variable Valid data window value Variable code Table 21 Alarm Impulse output 0 to 100% Pre-alarm value Table 41 Minimum value...
Page 217
CVM-B150-ITF-HF Table 85: Modbus memory: Transistor digital outputs, expansion modules (Table 3)� Transistor Digital Outputs configuration: Slot 2 Configuration variable Address Impulse Output Output Output Output Output Output Output Output Alarm output Energy Maximum value C738 C74C C760 C774 C788...
Page 218
CVM-B150-ITF-HF Table 87: Modbus memory map: Transistor digital outputs, expansion modules (Table 5)� Transistor Digital Outputs configuration: Slot 4 Configuration variable Address Impulse Output Output Output Output Output Output Output Output Alarm output Energy Maximum value CF08 CF1C CF30 CF44...
Page 222
CVM-B150-ITF-HF Table 100: Modbus memory map: Status of digital inputs (Table 3)� Status of digital inputs: Slot 3 Configuration variable Address Valid data window 0 to 1 Input Status 1 CD78 - CD79 Input Status 2 CD7A - CD7B 0 to 1...
Page 223
CVM-B150-ITF-HF Table 102 (Continuation): Modbus memory map: Status of transistor digital outputs (Table 1)� Status of transistor digital outputs Configuration variable Valid data window Impulse Impulse Alarm Alarm output output Not used Not used 0: No alarm, Status (62) 1: Active alarm,...
Page 224
CVM-B150-ITF-HF Table 104: Modbus memory map: Status of transistor digital outputs (Table 3)� Transistor digital outputs: Slot2 Configuration variable Address Impulse Output Output Output Output Output Output Output Output Alarm output Latch kWh o Wh CA58 CA6C CA80 CA94 CAA8...
Page 225
CVM-B150-ITF-HF Table 105 (Continuation):Modbus memory map: Status of transistor digital outputs (Table 4)� Transistor digital outputs: Slot3 Configuration variable Address Not used CE4B CE5F CE73 CE87 CE9B CEAF CEC3 CED7 Status CE4C CE60 CE74 CE88 CE9C CEB0 CEC4 CED8 Alarm Status...
CVM-B150-ITF-HF 7�4�- ANALOGUE INPUTS/OUTPUTS This expansion module contains 8 analogue outputs and 4 analogue inputs. 7�4�1�- CONNECTION TERMINALS A�- Terminals on the upper face Table 107: List of terminals on the upper face, Analogue inputs/outputs module� Device terminals 1: O...
Page 227
CVM-B150-ITF-HF B�- Terminals on the lower face Table 108: List of terminals on the lower face, Analogue inputs/outputs module� Device terminals 10: I +, Analogue input 1 14: I +, Analogue input 3 11: I -, Analogue input 1 15: I...
CVM-B150-ITF-HF 7�4�3�- CONFIGURATION Access the configuration menu, as described in , and enter the configuration icon “5.6.- SETUP MENU” of the expansion modules, The main screen of the expansion modules is shown in Figure 270 Figure 270: Main screen of expansion modules�...
Page 230
CVM-B150-ITF-HF The following options appear in the lower area: > > < < Analog inputs Main Analog menu Outputs Volver > > < < Figure 272: Setup menu : analogue inputs/outputs� Use the keys to select the different options. To confirm the selection, press the key 7�4�3�1�-...
Page 231
CVM-B150-ITF-HF > > < < Input1...4 Main varh Back menu > < Figure 274: Setup menu :Analogue inputs� Use the keys to select the different options. To confirm the selection, press the key When selecting the input to configure, the configuration parameters are: Figure 275, The analogue input scale.
Page 232
CVM-B150-ITF-HF > > > < < > < < Con guration Previous Main values menu Next Back Con rm Delete Delete and save parameter character > > < < > > < < Figure 276: Setup menu : Analogue inputs Use the keys to select the different options.
Page 233
CVM-B150-ITF-HF 7�4�3�2�- Analogue outputs� Select the output to configure on the main configuration screen for the analogue outputs, Figure 277 Figure 277: Main configuration screen for analogue outputs� > > < < Output 1...8 Main varh Back menu > <...
Page 234
CVM-B150-ITF-HF Figure 279: Analogue outputs configuration screen� The parameter selected is indicated in white. > > > < < > < < Con guration Previous Main values menu Next Back Con rm Delete Delete and save parameter character > >...
CVM-B150-ITF-HF ● When programming the Zero and the Full-scale value: Zero is the value for which you have the start of the analogue output, 0 or 4mA. The Full-scale is the value for which you have the end of the analogue output, 20mA.
Page 239
CVM-B150-ITF-HF 7�4�4�3�- Status of the analogue inputs The following functions are implemented for these variables: Function 0x04: reading registers. Table 120: Modbus memory map: Analogue inputs, expansion modules (Table 6)� Status of the analogue inputs: Slot 1 Configuration variable Address...
CVM-B150-ITF-HF 7�5�- MODBUS/TCP BRIDGE COMMUNICATIONS MODULE The M-CVM-AB-Modbus TCP (Bridge) is a communications module for connecting the CVM-B 150 devices to a Modbus/TCP network and as an Ethernet to RS-485 gateway. Modbus/TCP is a communications protocol designed for enabling industrial devices to communicate with each other on Ethernet networks using TCP/IP protocols.
Page 242
CVM-B150-ITF-HF Note : If in the device there is more than one module of the same type connected, a number will appear in the icon to differentiate; the module with the lowest number has the lowest serial number. Select the Modbus TCP (Bridge) communications icon, Figure 285�...
Page 243
CVM-B150-ITF-HF 7�5�4�1�- Configuration of DHCP activation/deactivation On this screen you select whether or not the IP is automatically assigned. Figure 287 Figure 287: Configuration screen of the Modbus TCP (Bridge) module ( TCP Auto) > > < < Con guration...
Page 244
CVM-B150-ITF-HF 7�5�4�2�- Configuration of the TCP parameters manually� Note: If DHCP is activated, you will not be able to modify the parameters on this screen. This is indi- cated by a * next to each value. The configuration parameters of the TCP communication are, Figure 289 IP address.
Page 245
CVM-B150-ITF-HF 7�5�4�3�- Configuration of the RS-485 gateway parameters The configuration parameters of the RS-485 gateway are, Figure 291 The transmission speed, Baud rate. The parity. The number of stop bits. Figure 291: Configuration screen of the Modbus TCP (Bridge) module (RS-485 Gateway) The parameter selected is indicated in white.
CVM-B150-ITF-HF ● When programming the transmission speed, Baud rate, the configuration values are: Possible transmission speeds: 9600, 19200, 38400, 57600, 76800 or 115200� ● When programming the parity: Even parity, Odd parity, No parity. ● When programming the number of stop bits: Possible numbers of stop bits: 1 or 2�...
Page 247
CVM-B150-ITF-HF 7�5�5�3�- Configuration of the RS-485 gateway parameters Table 128:Modbus memory map: Modbus TCP (Bridge) communications module (Table 3) Configuration of the Modbus TCP parameters Configuration variable Address Valid data margin Default value 0: 1200 - 1: 2400 - 2: 4800 -...
CVM-B150-ITF-HF 7�6�- LONWORKS COMMUNICATIONS MODULE The LonWorks communications module, M-CVM-AB-LON, enables communicating the CVM-B150 on a LonWorks network. 7�6�1�- CONNECTION TERMINALS Table 130: List of terminals, LonWorks communications module� Terminals in the device 1, 4: A, Bus connection ( without polarity )
CVM-B150-ITF-HF 7�6�3�- CONFIGURATION Access the configuration menu, as described in , and enter the configuration icon “5.6.- SETUP MENU” of the expansion modules, The main screen of the expansion modules is shown in Figure 295. Figure 295: Main screen of expansion modules�...
Page 250
CVM-B150-ITF-HF This screen can be used for connecting the device to a LonWorks network. To do so, select the confirm option . The device will then send to the network all the information needed to establish the connection. When the information has been sent correctly the following message appears on the screen,...
Function 0x04: reading registers. Function 0x10: Writing multiple registers. For this variable Function 0x04 is implemented. (65) 7�6�5�- LIST OF LONWORKS LOGS Note: The binary files and setup file can be downloaded from Circutor’s website. Variable Name Variable type Unit...
Page 252
CVM-B150-ITF-HF Variable Name Variable type Unit nvo_Ph2NU3 SNVT_volt_ac (138) Phase-Neutral Voltage L3 Code Resolution Values 0..65,534 Name Variable type Unit nvo_Frequency SNVT_freq_hz (76) Frequency Code Resolution Values 0..6553.5 Name Variable type Unit nvo_ActPwrPh1 SNVT_power_kilo (28) kW L1 Active Power L1...
Page 253
CVM-B150-ITF-HF Variable Name Variable type Unit nvo_PwrFactPh2 SNVT_pwr_fact (98) PF L2 Power factor L2 Code Resolution Values 0.00005 -1.00000..1.00000 Name Variable type Unit nvo_PwrFactPh3 SNVT_pwr_fact (98) PF L3 Power factor L3 Code Resolution Values 0.00005 -1.00000..1.00000 Name Variable type Unit...
Page 254
CVM-B150-ITF-HF Variable Name Variable type Unit nvo_MaxDemand_A3 SNVT_amp_ac (139) Md(A3) Current Maximum Demand L3 Code Resolution Values 0..65,534 Name Variable type Unit nvo_MaxDemand_A SNVT_amp_ac (139) Md(A III) Md Current III Code Resolution Values 0..65,534 Name Variable type Unit nvo_MaxDemand_kw SNVT_power_kilo (28)
Page 255
CVM-B150-ITF-HF Arrray 1 tipo NVT ( SNVT_str_int (37)), Unit (N/A), Resolution (1), Values (0...65,565), Bytes (31) typedef struct { unsigned short char_set ; unsigned long wide_char [15] ; } SNTV_str_int; Name Variable type Unit nvo_Ph1Current SNVT_amp_ac (139) Code Resolution Values Current L1 0..65,534...
Page 256
CVM-B150-ITF-HF Arrray 1 tipo NVT ( SNVT_str_int (37)), Unit (N/A), Resolution (1), Values (0...65,565), Bytes (31) typedef struct { unsigned short char_set ; unsigned long wide_char [15] ; } SNTV_str_int; Name Variable type Unit nvo_ActEnergy SNVT_elec_kwh_I (146) kW.h(+) Active Energy (+)
Page 257
CVM-B150-ITF-HF Arrray 3 tipo NVT ( SNVT_str_int (37)), Unit (N/A), Resolution (1), Values (0...65,565), Bytes (31) typedef struct { unsigned short char_set ; unsigned long wide_char [15] ; } SNTV_str_int; Name Variable type Unit Name Variable type Unit nvo_Ph2NU3 SNVT_volt_ac (138)
CVM-B150-ITF-HF Notes: All the variables declared in the arrays are shown without a sign. All the power variables (SNVT_power_kilo type) are shown without a sign. There is a variable called nvi_UpdatePeriod that indicates the refresh time of the variables linked ...
CVM-B150-ITF-HF 7�7�4�- CONFIGURATION Access the configuration menu, as described in , and enter the configuration icon “5.6.- SETUP MENU” of the expansion modules, The main screen of the expansion modules is shown in Figure 302 Figure 302: Main screen of expansion modules�...
To confirm the selection, press the button. 7�7�5�- VARIABLES PROFIBUS GSD FILE Note: Profibus drivers for Scada can be downloaded from Circutor’s website. The configurations of the GSD modules are given in Figure 232� The table shows the module number, content (variable) and the total size of the module.
Page 262
CVM-B150-ITF-HF Module 1 Table 135: GSD modules (Module 1 - Mod 1�1) Mod 1�1 Phase-neutral voltage Symbol Bytes Address Units Voltage phase 1 00-01 Vx100 Voltage phase 2 10-11 Vx100 Voltage phase 3 20-21 Vx100 Table 136: GSD modules (Module 1 - Mod 1�2) Mod 1�2...
Page 263
CVM-B150-ITF-HF Module 2 Table 140: GSD modules (Module 2) Mod 2 Powers Symbol Bytes Address Units Active powers Active power Kw 1 04-05 Active power Kw 2 14-15 Active power Kw 3 24-25 Inductive reactive powers Inductive reactive power KvarL 1...
Page 264
CVM-B150-ITF-HF Module 4 Table 144: GSD modules (Module 4) Mod 4 Address Address Total tariff Symbol Bytes Units Tariff 1 Active Energy kwh III 500-501 Active Energy wh III Inductive Reactive Energy kvarhL III 503-504 Inductive Reactive Energy varhL III...
CVM-B150-ITF-HF 7�8�3�- CONFIGURATION Access the configuration menu, as described in , and enter the configuration icon “5.6.- SETUP MENU” of the expansion modules, The main screen of the expansion modules is shown in Figure 307 Figure 307: Main screen of expansion modules�...
Page 267
CVM-B150-ITF-HF The configuration parameters are: The primary address The transmission speed, Baud rate. The parameter selected is indicated in white. The following options appear in the lower area: > > > < < > < < Con guration...
CVM-B150-ITF-HF 7�8�4�- MODBUS COMMUNICATIONS The following functions are implemented for this variable: Function 0x04: reading logs. Function 0x10: Writing multiple logs. Table 147:Modbus memory map: MBus communications module Configuration of the MBus parameters Configuration variable Address Valid data margin Default value...
Page 269
CVM-B150-ITF-HF 7�8�5�1�- TABLE OF “RSP_UD” TELEGRAM VARIABLES Variables arranged by order of appearance in the telegram. Table 148: Table of “RSP_UD” telegram variables� Variable Format Type Units Notes Date/time of the Date / Time 4 bytes type F Timestamp analyzer...
The embedded PowerStudio environment of the module can be used to display the data in real time, as well as the data stored over time. Refer to the PowerStudio manual and tutorials found on CIRCUTOR’s website for more information about additional configurations, sending emails, generation of additional calculations, etc.
CVM-B150-ITF-HF 7�9�3�- CONNECTION DIAGRAM Con navegador Web With a browser compatible con HTML5 compatible with HTML5 With a browser compatible with HTML5 Con navegador Web compatible con HTML5 Opcional / Optional INTERNET SERVIDOR/ SERVER ROUTER Ethernet CVM B-1xx M-CVM-B-Datalogger Servidor Web...
CVM-B150-ITF-HF 7�9�4�- CONFIGURATION Access the configuration menu, as described in , and enter the configuration icon “5.6.- SETUP MENU” of the expansion modules, The main screen of the expansion modules is shown in Figure 313 Figure 313: Main screen of expansion modules�...
Page 273
CVM-B150-ITF-HF > > < > < < Main TCP auto menu Back manual Port > > < < Figure 315: Setup menu : Datalogger module� Use the buttons to select the different options. To confirm the selection, press the button.
Page 274
CVM-B150-ITF-HF > > < < Con guration values Main Con rm menu and save > Back > < < Figure 317:Setup menu : Datalogger module� (TCP Auto)� Use the buttons to select the different options. To confirm the selection, press the button.
Page 275
CVM-B150-ITF-HF The parameter selected is indicated in white. > > > < < > < < Con guration Previous Main values menu Next Back Con rm Delete Delete and save parameter character > > < < > > < <...
CVM-B150-ITF-HF > > < > < < Main menu Con guration values Delete Back character Con rm Delete and save parameter > > < < > < Figure 321: Setup menu : Datalogger module (Port)� Use the buttons to select the different options.
CVM-B150-ITF-HF 7�10�- MODBUS/TCP Switch COMMUNICATIONS MODULE The M-CVM-AB-Modbus TCP (Switch) is a communications module for connecting the CVM-B devices to a Modbus/TCP network and as an Ethernet to Ethernet gateway. Modbus/TCP is a communications protocol designed for enabling industrial devices to communicate with each other on Ethernet networks using TCP/IP protocols.
Page 279
CVM-B150-ITF-HF Select the Modbus TCP (Switch) communications icon, Figure 326� Figure 326: Main configuration screen of the Modbus TCP communications module� > > < < TCP auto Main menu manual > Back > < < Figure 327: Setup menu : Modbus TCP (Switch) communications�...
Page 280
CVM-B150-ITF-HF 7�10�4�1�- Configuration of DHCP activation/deactivation On this screen you select whether or not the IP is automatically assigned. Figure 328 Figure 328: Configuration screen of the Modbus TCP (Switch) module (TCP Auto) > > < < Con guration values...
Page 281
CVM-B150-ITF-HF 7�10�4�2�- Configuration of the TCP parameters manually� Note: If DHCP is activated, you will not be able to modify the parameters on this screen. This is indi- cated by a * next to each value. The configuration parameters of the TCP communication are, Figure 330 IP address.
CVM-B150-ITF-HF 7�10�5�- MODBUS COMMUNICATIONS The following functions are implemented for these variables: Function 0x04: reading registers. Function 0x10: Writing multiple registers. 7�10�5�1�- Configuration of DHCP activation/deactivation Table 155:Modbus memory map: Modbus TCP (Switch) communications module (Table 1) Configuration of DHCP activation/deactivation...
To update the device you will need: The microSD card inserted on one side of the device. The update files, which can be found on the Circutor web site. Select the update files A PC so as to update the files in the microSD card.
CVM-B150-ITF-HF 8�1�- DEVICE SOFTWARE UPDATE� The update files depend on the model of the device: Table 158:Display software update files� Model Display software update file firmware_cpu.bin CVM-B150 resources_CVM_B150.pbr resources_CVM_B150_cp.pbr Follow the steps below to update the device software: 1�- Copy the 3 files, , in the microSD card.
CVM-B150-ITF-HF The updated information on the modules is displayed in the expansion modules section of the information menu, “5.5.3.- EXPANSION MODULES.” Figure 333:Expansion modules information screen� The update files are not deleted automatically from the microSD card. This is in case you want to add a new module afterwards and want it to be updated with the same version of the modules already installed.
Page 286
Upgrade button. Figure 335: Datalogger module upgrade screen� Note: The upgrade files can be found on Circutor’s website. 4�- Do not turn off the device during the upgrade process. 5�- When the firmware of the module has been upgraded, check that the version is shown in the in- formation menu (“5�5�3�7�- Datalogger expansion modules”) corresponds to the upgraded version.
CVM-B150-ITF-HF 9.- TECHNICAL FEATURES AC power supply Rated voltage 100 ... 240 V ~ Frequency 45 ... 65 Hz Consumption max. 29.4 VA Installation category CAT III 300 V DC Power supply Rated voltage 120 ...300 V Consumption max.11.9 W...
Page 288
CVM-B150-ITF-HF (Continuation) Accuracy of measurements (in accordance with the IEC 61557-12 standard for PMD SD/SS) ���/5A ���/1A Power factor measurement Class 0.5 Class 0.5 Transistor digital outputs (66) Quantity Type Transistor Maximum voltage Maximum current 130 mA Maximum frequency 1 KHz...
Page 289
CVM-B150-ITF-HF Environmental features Operating temperature -10ºC ... +50ºC Storage temperature -20ºC ... +80ºC Relative humidity (without condensation) 5 ... 95% Maximum altitude 2000 m IP30 Protection degree Front panel without seal: IP40 (67) Front panel with seal: IP65 This pollution degree hasn’t been tested by UL.
CVM-B150-ITF-HF 10.- TECHNICAL FEATURES OF EXPANSION MODULES 10�1�- TRANSISTOR DIGITAL INPUTS/OUTPUTS General features Maximum power of the module Refresh time Response time (outputs) / Detection time (inputs) < 150 ms Transistor digital outputs (68) Quantity Type Maximum voltage 48 V...
CVM-B150-ITF-HF 10�2�- RELAY DIGITAL INPUTS/OUTPUTS General features Maximum power of the module Refresh time Response time (outputs) / Detection time (inputs) < 150 ms Relay digital outputs (70) Quantity Maximum voltage, open contacts 250 V~ Maximum current Maximum switching power...
CVM-B150-ITF-HF 10�3�- DIGITAL ANALOGUE INPUTS/OUTPUTS General features Maximum power of the module Refresh time Response time (outputs) / Detection time (inputs) < 150 ms Analogue outputs (72) Quantity Maximum internal voltage 12 V Linearity <1% DAC resolution 4096 dots Analogue outputs in current mode...
CVM-B150-ITF-HF (Continuation) Standards Safety requirements for electrical equipment for measurement, control, and labo- UL 61010-1 3rd edition, 2012- ratory use - Part 1: General requirements Safety Requirements for Electrical Equipment for Measurement, Control and Labo- CAN/CSA-C22.2 No. 61010-1, ratory Use - Part 1: General Requirements (Adopted IEC 1010-1:1990 with modifica-...
CVM-B150-ITF-HF Safety Requirements for Electrical Equipment for Measurement, Control and Lab- CAN/CSA-C22.2 No. 61010-1, 3rd oratory Use - Part 1: General Requirements (Adopted IEC 1010-1:1990 with modi- edition, 2012-05 fications) 10�5�- LONWORKS COMMUNICATIONS General features Maximum power of the module 1.2 W...
CVM-B150-ITF-HF 10�6�- PROFIBUS COMMUNICATIONS General features Maximum power of the module Communications Connector Protocol Profibus Identifier Baud rate 19,2 kbs - 93,75 kbs - 187,5 kbs - 500 kbs - 1500 kbs - 3000 kbs - 6000 kbs - 12000 kbs...
CVM-B150-ITF-HF 10�7�- MBUS COMMUNICATIONS General features Maximum power of the module Communications Wired M-Bus Protocol Slave M-Bus compatible to EN 13757-2 and EN 13757-3 Baud rate 1200 - 2400 - 4800 - 9600 Primary address 1 ... 250 Stop bits...
CVM-B150-ITF-HF 10�8�- DATA STORAGE, DATALOGGER General features Maximum power of the module Communications : XML communications Connector RJ-45 Protocol Baud rate Ethernet 10BT / 100BT Environmental features Operating temperature -10ºC ... +50ºC Storage temperature -20ºC ... +80ºC Relative humidity (without condensation) 5 ...
CVM-B150-ITF-HF 10�9�- MODBUS TCP (Switch) COMMUNICATIONS General features Maximum power of the module Communications : Modbus TCP Connector RJ-45 Protocol Modbus/TCP Baud rate Ethernet 10BT / 100BT Environmental features Operating temperature -10ºC ... +50ºC Storage temperature -20ºC ... +80ºC Relative humidity (without condensation) 5 ...
The device does not need any maintenance. Only clean the screen with soapy water and dry with a soft dry cloth. In the case of any query in relation to device operation or malfunction, please contact the CIRCUTOR S�A�U� Technical Support Service.