Circutor CVM-C11 Instruction Manual page 24

Power analyzer
Hide thumbs Also See for CVM-C11:
Table of Contents

Advertisement

3�5�11�- MEASURING TWO-PHASE NETWORKS WITH A 3-WIRE CONNECTION, CVM-C11-MC-IN-485-
ICT2 MODEL
Note: Do not connect MC current transformers to ground.
24
Measurement system:
U
N
U
L2
L1
a
b
a
b
A
B
A
B
L1
L2
N
CARGA /LOAD
Figure 14: Measuring Two-Phase Networks with a 3-wire connection (CVM-C11-MC-IN-485-ICT2)�
The MC transformer secondary value is set to 0.250 A (fixed value).
3-2Ph