Filter Specifications; Passive Harmonic Filter Specifications; Line Reactor Specifications - Danfoss VLT AQUA Drive FC 202 Operating Manual

110-800 kw, enclosures d9h-d10h and e5h-e6h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202
+24 V
Control
18
37
Functional
isolation
RS485
Illustration 71:
PELV Isolation

10.7 Filter Specifications

10.7.1 Passive Harmonic Filter Specifications

Phase imbalance
Voltage variation
Nominal frequency
Overload capability
Maximum inrush current, drive side
Maximum inrush current, PHF input side
Cos of IL at 25% IPHF, N
Cos of IL at 50% IPHF, N
Cos of IL at 75% IPHF, N
Cos of IL at 100% IPHF, N
Cos of IL at 160% IPHF, N
Power derating

10.7.2 Line Reactor Specifications

All line reactors are equipped with thermal switches and are looped to the enclosed drive for overtemperature protection. For more
details, refer to the control compartment section. The line reactor configuration varies depending on the enclosure and voltage
required.
Table 86: Line Reactor Configuration for D9h–D10h and E5h–E6h Enclosures, 380–480 V
Enclosure
D9h
D10h
176 | Danfoss A/S © 2018.10
PELV isolation
Mains
High
Motor
voltage
DC-bus
Model
N110
N132
N160
N200
N250
N315
Maximum of 3% (Drives have to be functional up to 8%)
-2%, +2% (of 50 Hz or 60 Hz) when PHF is installed
150% for 60 s in a period of 10 minutes
Line reactor [A]
312
312
425
425
2x312
2x312
AQ262141056213en-000101 / 130R0882
Specifications
+10%–15%
Maximum 5xI
nom drive
Maximum 2xI
nom drive
0.85 Ind
0.88 Ind
0.92 Ind
0.99 Ind
0.98 Ind
Same as drive

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT AQUA Drive FC 202 and is the answer not in the manual?

Subscribe to Our Youtube Channel

Table of Contents