Operating Guide | VLT® AQUA Drive FC 202

5.8.5 Connecting the dU/dt Filter to the Motor

Procedure
1. Strip a section of the outer cable insulation.
2. Fasten a connector/cable lug to the end of the stripped cable.
3. Create an electrical connection between the cable shield and ground by securing the stripped wire under the cable clamp.
4. Connect the ground cable to the nearest grounding terminal in accordance with the grounding instructions provided in
Connecting to
Ground.
5. Connect the 3-phase AC motor wiring to the dU/dt terminals U (T1), V (T2), and W (T3).
6. Tighten the terminals in accordance with the specifications shown in
Danfoss A/S © 2018.10
10.11 Fastener Torque
Ratings.
AQ262141056213en-000101 / 130R0882 | 89
Electrical Installation
5.8.6