Danfoss VLT AQUA Drive FC 202 Operating Manual page 162

110-800 kw, enclosures d9h-d10h and e5h-e6h
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

Operating Guide | VLT® AQUA Drive FC 202
FC 202
- Mains with disconnect [mm
- Mains with fusible disconnect [mm
- Mains with contactor [mm
2
- Mains [mm
(AWG)]
Drive module power loss at 400 V [W]
Drive module power loss at 460 V [W]
Drive efficiency
(2)
Output frequency [Hz]
(4)
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
PHF overtemperature trip [°C (°F)]
dU/dt filter overtemperature trip [°C (°F)]
Sine-wave filter overtemperature trip [°C (°F)]
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These values are based on a typical motor
efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimensioning of drive cooling. If the switching frequency is higher than the default
setting, the power losses can increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/
knowledge-center/energy-efficiency-directive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B
each add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficiency class, see the Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also Input Power Option Losses.
4
If using an output filter, the output frequency is limited further. See the Motor Output (U, V, W) section.
Table 80: Electrical Data, Mains Supply 3x380–480 V AC
FC 202
High/normal overload
High overload=150% or 160% torque for a duration of 60 s.
Normal overload=110% torque for a duration of 60 s.
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Typical shaft output at 480 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400 V) [A]
Continuous (at 460/480 V) [A]
Intermittent (60 s overload) (at 460/480 V) [A]
162 | Danfoss A/S © 2018.10
2
(AWG)]
2
(AWG)]
2
(AWG)]
(1) (2) (3)
(1) (2) (3)
N200
N250
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
3093
4116
4039
2872
3569
3575
0.98
0.98
0–590
0–590
110 (230)
110 (230)
80 (176)
80 (176)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
150 (302)
N355
N400
HO
NO
HO
315
355
355
450
500
500
355
400
400
E5h
E5h
600
658
658
900
724
987
540
590
590
810
649
885
Specifications
N315
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
5137
5005
6674
4566
4458
5714
0.98
0–590
110 (230)
80 (176)
150 (302)
150 (302)
150 (302)
N450
NO
HO
NO
400
400
450
600
550
600
500
500
530
E5h
745
695
800
820
1043
880
678
678
730
746
1017
803
AQ262141056213en-000101 / 130R0882