Operating Guide | VLT® AQUA Drive FC 202
Table 106: Mains Contactor Fuses for N355–N560 Models, 380–480 V
N355
IEC
580 A/1000 V
Eaton P/N
XTCE580N22A
UL
820 A/1000 V
Eaton P/N
XTCE820N22A
Table 107: Mains Contactor Fuses for N110–N315 Models, 525–690 V
N110
IEC
185 A/1000 V
Eaton P/N
XTCE400H22A
UL
185 A/1000 V
Eaton P/N
XTCE400H22A
Table 108: Mains Contactor Fuses for N400–N630 Models, 525–690 V
N400
IEC
400 A/1000 V
Eaton P/N
XTCE400M22A
UL
400 A/1000 V
Eaton P/N
XTCE400M22A
Table 109: Mains Contactor Fuses for N710–N800 Models, 525–690 V
IEC
Eaton P/N
UL
Eaton P/N
10.8.6 Molded-case Circuit Breakers
The molded-case circuit breaker (MCCB) is an option that combines a temperature sensitive device with a current sensitive
electromagnetic device to protect the drive.
Table 110: MCCB Part Numbers for N110–N315 Models, 380–480 V
N110
IEC
400 A/600 V
ABB P/N
T5L400T
UL
400 A/690 V
184 | Danfoss A/S © 2018.10
N400
580 A/1000 V
XTCE580N22A
820 A/1000 V
XTCE820N22A
N132
N160
185 A/1000 V
185 A/1000 V
XTCE400H22A
XTCE400H22A
185 A/1000 V
185 A/1000 V
XTCE400H22A
XTCE400H22A
N450
580 A/1000 V
XTCE580N22A
580 A/1000 V
XTCE580N22A
N710
580 A/1000 V
XTCE580N22A
820 A/1000 V
XTCE820N22A
N132
N160
400 A/600 V
400 A/600 V
T5L400T
T5L400T
400 A/690 V
400 A/690 V
N450
N500
580 A/1000 V
820 A/1000 V
XTCE580N22A
XTCE820N22A
820 A/1000 V
1000 A/1000 V
XTCE820N22A
XTCEC10N22A
N200
400 A/1000 V
XTCE400M22A
400 A/1000 V
XTCE400M22A
N500
N560
580 A/1000 V
580 A/1000 V
XTCE580N22A
XTCE580N22A
580 A/1000 V
580 A/1000 V
XTCE580N22A
XTCE580N22A
N800
820 A/1000 V
XTCE820N22A
1000 A/1000 V
XTCEC10N22A
N200
800 A/600 V
T6L800T
600 A/690 V
Specifications
N560
820 A/1000 V
XTCE820N22A
1000 A/1000 V
XTCEC10N22A
N250
N315
400 A/1000 V
400 A/1000 V
XTCE400M22A
XTCE400M22A
400 A/1000 V
400 A/1000 V
XTCE400M22A
XTCE400M22A
N630
580 A/1000 V
XTCE580N22A
580 A/1000 V
XTCE580N22A
N250
N315
800 A/600 V
800 A/600 V
T6L800T
T6L800T
600 A/690 V
800 A/690 V
AQ262141056213en-000101 / 130R0882
Need help?
Do you have a question about the VLT AQUA Drive FC 202 and is the answer not in the manual?