Operating Guide | VLT® AQUA Drive FC 202
Table 103: Non-fusible Disconnect Switches for N400–N630 Models, 525–690 V
N400
IEC
630 A/600 V
ABB P/N
OT630E30
UL
600 A/690 V
ABB P/N
OT600U30
Table 104: Non-fusible Disconnect Switches for N710–N800 Models, 525–690 V
IEC
ABB P/N
UL
ABB P/N
10.8.5 Contactor Fuses
The mains contactor is an option. All units ordered and supplied with a factory-installed contactor require a Class L/J branch circuit
fusing to meet the 65 kA SCCR for the drive system.
This option makes it possible to connect or disconnect the drive from the mains by using a control switch on the control compartment
door or an external switch. The external switch must be wired to terminals XD0. See
Drives
and
5.4 Wiring Schematic for E5h and E6h Enclosed
normally open and 1 normally closed). These switches are on the sides of the contactor. By default, the NO auxiliary switch is wired at
the factory and used by the system.
Auxiliary switch specifications
Rated operation current @ 230 V
Rated operation current @ 380 V
Rated operation current @ 480 V
Conventional thermal current, Ith
Rated voltage
Rated impulse withstand voltage
Table 105: Mains Contactor Fuses for N110–N315 Models, 380–480 V
N110
IEC
185 A/1000 V
Eaton P/N
XTCE400M22A
UL
185 A/1000 V
Eaton P/N
XTCE400M22A
Danfoss A/S © 2018.10
N450
630 A/600 V
OT630E30
600 A/690 V
OT600U30
N710
1250 A/600 V
OT1250E30
1200 A/690 V
OT1200U30
Drives. The mains contactor is supplied with 2 sets of auxiliary switches (1
N132
N160
185 A/1000 V
185 A/1000 V
XTCE400M22A
XTCE400M22A
185 A/1000 V
185 A/1000 V
XTCE400M22A
XTCE400M22A
N500
N560
630 A/600 V
1000 A/600 V
OT630E30
OT1000E30
600 A/690 V
800 A/690 V
OT600U30
OT800U30
N800
1250 A/600 V
OT1250E30
1200 A/690 V
OT1200U30
5.3 Wiring Schematic for D9h and D10h Enclosed
N200
400 A/1000 V
XTCE400M22A
400 A/1000 V
XTCE400M22A
Specifications
N630
1000 A/600 V
OT1000E30
800 A/690 V
OT800U30
N250
N315
580 A/1000 V
500 A/1000 V
XTCE400M22A
XTCE500M22A
400 A/1000 V
580 A/1000 V
XTCE580N22A
XTCE580N22A
AQ262141056213en-000101 / 130R0882 | 183
6 A
4 A
1.5 A
10 A
500 V AC
600 V AC
Need help?