Operating Guide | VLT® AQUA Drive FC 202

5.7.6 Overview of Options Wiring

5.7.6.1 Auxiliary Supply Terminals
Table 33: Auxiliary Supply Codes
Character position
21
The auxiliary supply terminal option provides an external voltage supply to the –XD1.1 terminal. The external supply must be short-
circuit protected. The power of the external supply depends on other selected cabinet options.
-FC6
-XD1.1
2
10 A
Illustration 42:
Auxiliary AC Supply Terminals
HIGH VOLTAGE
The mains disconnect switch does not disconnect the external voltage supply. Failure to disconnect the external voltage supply
before touching any components in the control compartment can result in death or serious injury.
Disconnect the external voltage supply.
-
Only qualified personnel must install, start up, and maintain the drive.
-
5.7.6.2 Auxiliary Voltage Transformer
Table 34: Auxiliary Supply Codes
Character position
21
The auxiliary voltage transformer is an option fitted internally that allows for the supply to be tapped from the mains. If the enclosed
drive is specified with a fused disconnect, the supply for the auxiliary voltage transformer is taken from between the drive and the
fused disconnect. This configuration allows the control voltage to be disconnected with the main switch.
72 | Danfoss A/S © 2018.10
Option code
1
5
6
9
W A R N I N G
Option code
2
4
7
8
Description
230 V AC external
230 V AC external + 24 V DC internal
120 V AC external
120 V AC external + 24 V DC internal
-XD1
Description
230 V AC internal
230 V AC internal + 24 V DC internal
120 V AC internal
120 V AC internal + 24 V DC internal
Electrical Installation
AQ262141056213en-000101 / 130R0882