Attributes; Associated Timer; Times; Oscillation - Bentel Security KYO 320 Installation Manual

Expandable multifunction control panel
Hide thumbs Also See for KYO 320:
Table of Contents

Advertisement

Control Panel and terminals [ T ] on Output Expanders
are open.
Normally Closed The electrical state during standby
is: Positive signal (13.8V) on the [+N] terminals; [+A]
terminals open; [C] terminals closed to their respective
terminals [NC]; [NO] terminals open; terminals [OC] on
the Control Panel and terminals [ T ] on Output Expand-
9
ers
are closed to Negative.
n Attributes
Reserved This Attribute will allow the User to acti-
vate/stop the Output from the Keypad or via telephone
(refer
to
"Activating
OPERATIONS" in the PROGRAMMING FROM KEYPAD
MANUAL, and to the "OPERATIONS VIA TELEPHONE"
section in the USER MANUAL).
+
Reserved Outputs CANNOT be associated with
the Events on the Events-Actions page.
+
When you exit a programming session via PC, Mo-
dem or Keypad, the Reserved Outputs will restore
to the status they were in before the programming
session started.
Output followed This field will allow you to associate
the selected Output with another Output. The selected
Output will track the specified Output (i.e. be activated
by the same Events, and perform the same Actions).
If you DO NOT want the selected Output to track an-
other Output, you must select "None" in this field. An
Output that is programmed to track another Output will:
Ø activate when the specified Output activates;
Ø restore to standby when the "tow" Output restores to
standby.
+
If you program an Output to track another Output,
you will not be able to associate it with the Events
on the Events-Actions page.
Supervised If the system has been duly set
up, this Attribute will allow the system to monitor
the Output for short circuits and interrupted con-
nections (refer to NOTE).
+
This Attribute can be selected for Out-
puts no. 1, 2 and 3 .
NOTE: Terminal [+A] must be wired in accor-
dance with the instructions in the "Supervised
Outputs" paragraph (refer to the "INSTALLA-
TION" section under "Connecting Signalling
Devices"), otherwise, the system will be un-
able to signal short circuits and interrupted
connections on the Supervised Outputs.
n Associated Timer
This section will allow you to associate a
Timer with the Output. The Output can be ac-
tivated ONLY by the selected Timer (refer to
"Time Programmer - Timer").
KYO 320
Outputs"
under
"KEYPAD
Figure 31 Partitions page
PROGRAMMING FROM THE PC
+
9
When the Timer window expires, the Output will re-
store to standby, even if the conditions that gener-
ated the event are still present.
n Times
This section will allow you to set the On/Off Times of
the Output.
+
The ON Time and OFF Time can be set for Mono-
stable Outputs only.
ON Time This is the maximum activation time of the
Output.
Valid entries:
Ø 0.2 through 25.4 seconds, in 0.2-second steps (for
sec. option)
Ø 1 through 127 minutes, in 1-minute steps (for Min.
option)
Default setting: 3 minutes
OFF Time This is the minimum OFF Time after restoral
of the Output. The Output will be unable to re-activate
until the programmed OFF Time expires.
Valid entries: 1 through 255 seconds, in 1-second steps.
Default setting: 3 minutes
n Oscillation
Outputs with this attribute will remain active for the pro-
grammed time, return to standby for the same amount
of time, and then reactivate. Oscillating Outputs can be
used to generate visual and audible signals (cause
LEDs to blink or buzzers to sound).
Oscillation parameters
Half Cycle This field will allow you to program the amount
of time the Output will be active, and the amount of time it
will be in standby status during Oscillation.
Valid entries: 200 msec (milliseconds) through 1400 msec
in 200 msec steps; If you set 0, the Output will not oscillate.
45