Glass Break Detectors - Bentel Security KYO 320 Installation Manual

Expandable multifunction control panel
Hide thumbs Also See for KYO 320:
Table of Contents

Advertisement

Ø [NC] terminals are the Normally Closed Alarm Con-
tacts of the detector;
Ø [AS] terminals are the Normally Closed Tamper Con-
tacts of the detector.
Normally Closed The wiring diagram in Fig. 12 illus-
trates the connection of a detector to a zone with Nor-
mally Closed balance.
Normally Closed balance will allow the Control panel to
detect Alarm status on the zone:
– the zone will hold Standby status whilst connected to
negative;
– the zone will trigger Alarm under all other conditions.
To provide Tamper detection: connect the Tamper con-
tact of the detector to the Control panel Tamper Line, or to a
24h zone (refer to "Connecting Tamper Contacts").
10 K The wiring diagram in Fig. 13 illustrates the con-
nection of a detector to a zone with 10 K, or 10 K Alarm
Only balance.
!
The 10 KW resistor must be connected to the
last detector of the zone.
10 K balance will allow the Control panel to detect
Alarm and Short-circuit on the zone:
– the zone will hold Standby status when connected to
negative via a10 KW resistor;
– the zone will trigger short-circuit when connected to
negative;
– the zone will trigger Alarm under all other conditions.
To provide Tamper detection: connect the Tamper con-
tact of the detector to the Control panel Tamper Line, or
to a 24h zone (refer to "Connecting Tamper Contacts").
10 K Alarm Only The wiring diagram in Fig. 13 illus-
trates the connection of a detector to a zone with 10 K,
or 10 K Alarm Only balance.
Input Expander
+F
T1
+F
L1
Panel
Figure 14 Connecting a Detector to a zone with Dou-
ble balance
KYO 320
!
10 K Alarm Only balance will allow the Control panel to
detect Alarm status on the zone:
– the zone will hold Standby status when connected to
negative via a10 KW;
– the zone will trigger Alarm under all other conditions.
Double The wiring diagram in Fig. 14 illustrates the
connection of a detector to a zone with Double balance.
This type of zone will allow the Control panel to detect
zone Alarm, Tamper and Short-circuit:
– the zone will hold Standby status whilst connected to
negative via a 5 KW resistor (i.e. using two 10 KW resis-
tors connected in parallel);
– the zone will trigger short-circuit when connected to
negative;
– the zone will trigger Tamper when open;
– the zone will trigger Alarm under all other conditions.
+
To provide Tamper detection on zones with Normally
Closed or 10 K balance:
either connect the detector tamper contact to the Con-
trol panel Tamper Line — this type of connection does
not provide identification of the tampered detector;
or connect the detector tamper contact to a 24h zone —
this type of connection requires two zones — one for
Alarm detection, and the other for Tamper detection (re-
fer to "Connecting Tamper Contacts").
n Glass Break Detectors
Fig. 15 illustrates the connection of 3 Glass Break de-
tectors to a zone with Glass Break balance.
+F
+F
Keypad
N. C. A.
S.
Detector
Figure 15 Connecting 3 Glass Break Detectors to a
zone with Glass Break balance
INSTALLING
The 10 KW resistor must be connected to the
last detector of the zone.
Zones with Double balance can detect and signal
Alarm and Tamper by means of just two wires.
Input Expander
T1
Panel
L1
glass
glass
break
break
detector
detector
Keypad
glass
break
detector
23

Advertisement

Table of Contents
loading

Table of Contents