8. Set the operating mode using microswitches 6 and
7 on DIP switch 80 as shown in the following table:
Microswitch No.
6
7
OFF
OFF
Input Expander with 6 Inputs
ON
OFF
Input Expander with 4 Inputs +
Output Expander with 2 Out-
puts (T1 and T2 Outputs; T3,
T4, T5 and T6 Inputs)
OFF
ON
Output Expander with 4 Out-
puts + Input Expander with 2
Inputs (T1, T2, T3 and T4 Out-
puts; T5 and T6 Inputs)
ON
ON
Output Expander with 6 Outputs
9. Set the operating mode of the Inputs using
microswitch 8 on DIP switch 80 as shown in the foll
owing table:
Microswitch
No.8
All Inputs operate in Normal
OFF
mode
All inputs operate in Normal
mode and function as inter-
face for Roller blind contact.
ON
Zone will trigger alarm accord-
ing to programmed sensibility
or if 5 pulses will be noticed, in
the time of two minutes
10. Replace the frontplate.
+
The Roller-blind attribute can only be reset via
hardware, through microswitch n.97, and not by
software, through the package Bentel Suit (the
Roller-blind attribute, for the M-IN/OUT expander
zones, is blocked).
+
Be careful about the position of conductive pin 108,
located inside the cover: it must close the Tamper
switch Contact 98 on the PCB (component side).

Terminals

This section describes the Main Unit and BPI device ter-
minals.
The layout of Terminal Description table is as follows:
Ø the Ter. column shows the terminal identifier;
Ø the DESCRIPTION column provides a brief descrip-
tion of each terminal;
Ø the v(V) column shows the terminal voltage (the hy-
phen "–" indicates that the voltage cannot be speci-
fied for the terminal concerned);
Ø the I(A) column shows the maximum current (in Am-
peres) that can circulate on the terminal (the hyphen
KYO 320
OPERATING MODE
OPERATING MODE FOR
INPUTS
"–" indicates that the current cannot be specified for
the terminal concerned);
Ø the numbers in brackets refer to the following notes.
(1) The total current draw of Main Unit terminals [+A3],
[+N3], [+A2], [+N2], [+A1], [+N1], [+B4], [+B5], [+F],
[+F1], [+] and [RED] must not exceed 3.8A for KYO320.
(2) The current draw of BPI device [+] terminals is:
Ø Keypad = 0.06 A for PREMIUM (with Proxi enabled),
and 0.05 A (with Proxi disabled),
0.05A for CLASSIKA
Ø Reader = 0.03 A
Ø M-IN/OUT Input/Output Expander = 0.02 A.
+
These values refer to the current draw of the BPI
devices with no loads.
(3) The sum of the currents absorbed by the terminals
[+F] of an M-IN/OUT Input/Output Expander must not
exceed 0.4 A.
(4) The terminals T of M-IN/OUT Expander can switch
up to 0.1 A. To switch higher currents use the
CNM004R Relays card.
n Main Unit
Ter.
NA3
Programmable
NC3
(changeover switch contacts)
C3
+A3 Programmable Output no.3 (posi-
tive), protected by fuse
+N3 Programmable Output no. 3 (in-
trinsic security), protected by fuse
NA2
Programmable
NC2
(changeover switch contacts)
C2
+A2 Programmable Output no. 2 (posi-
tive), protected by fuse
+N2 Programmable Output no. 2 (in-
trinsic security), protected by fuse
NA1
Programmable
NC1
(changeover switch contacts)
C1
+A1 Programmable Output no. 1 (posi-
tive), protected by fuse
+N1 Programmable Output no. 1 (intrin-
sic security), protected by fuse 46
+B4 Positive power supply to peripher-
als, protected by fuse
powered by the battery during
Mains failure)
+B5 Positive power supply to peripher-
als, protected by fuse
powered by the battery during
Mains failure)
M Negative
OC1 Programmable
(Open-Collector)
INSTALLING
DESCRIPTION
Output
no.
3
Output
no.
2
Output
no.
1
(will be
(will be
Output
no.
4
v(V) I(A)
3
13.8 3(1)
13.8 3(1)
3
13.8 3(1)
13.8 3(1)
3
13.8 3(1)
13.8 3(1)
13.8 3(1)
3(1)
0
0
1
17