Step 8: Parameter Overview-Quick Setting Menu (Simplex) - YASKAWA iQpump Micro Quick Start Manual

Ac drive compact intelligent pump controller quick start procedure
Hide thumbs Also See for iQpump Micro:
Table of Contents

Advertisement

iQpump Micro
Quick Start Procedure
STEP
Parameter Overview-Quick Setting Menu (Simplex)
8
Task
8.1 Read-only parameter. It
cannot be modifi ed. Factory set
to (0: Pressure control)
8.2 Set to the motor nameplate
full load amps
Set service factor amps (SFA).
for submersible motors use
8.3 Enter '4' for an 1800 RPM
motor and '2' for a 3600 RPM
motor.
Confi rm number of poles:
2 Pole Motor = 3600 RPM
4 Pole Motor = 1800 RPM
6 Pole Motor = 1200 RPM
8 Pole Motor = 900 RPM
8.4 System Scaling: Enter
feedback device maximum:
Example: Enter 200 for
pressure transducer with a
maximum of 200 PSI at 20mA.
Confi rm feedback device
scaling.
(See Illustration 1)
8.5 Set to system pressure
8.6 Choose one of two types of
Start Level programming:
1. Program the Start Level as
an Absolute
OR
2. Program the Start Level as
a Delta Level from the System
Setpoint
Parameter
Name
A1-06
Application Preset
E2-01
Motor Rated Current
E2-04
Number of Motor
Poles
P1-03
Feedback Device
Scaling
Q1-01
PID Controller
Setpoint 1
P1-04
Start / Drawn Down
Level
Description/Menu Access
Displays selected applications, see Step 5.
Motor nameplate full load amps.
Sets the number of motor poles.
Number of motor poles is used to show the
correct motor RPM on the display
Sets the scaling of feedback device in user-
set units.
Sets the PID Setpoint when b1-01 is set to 0. 0.0
The system starts when the feedback level
drops below the start level for the time set
in P1-05 (default 1 sec). This level also
specifi es the wakeup level when the drive is
in Sleep Mode. When this parameter is set
to a negative value, the feedback level must
drop that amount below the setpoint. Setting
this parameter to 0.0 disables the function.
When P1-01, Pump Mode, is set to 3
(MEMOBUS network), this function is active
only on the fi rst drive in the network.
YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure
Page 21
of 31
Default Value
Factory set to
(0: Pressure
control).
Dependent on
Initialization
Mode
Drive Size
Dependent
2
145.0
0.0 PSI