Bypass Status Messages - YASKAWA HV600 Installation & Startup

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.10

Bypass Status Messages

The bypass HOA keypad will show these status messages on line 1 of the keypad display during the conditions listed
below. These are not faults or alarms.
Keypad Display
Powering Up
Idle
Drive Not Ready
Safety Open
Fire Stat Open
Freeze Stat Open
Smoke Alarm active
Over Pressure Detected
Low Suction Detected
Vibration Detected
Interlock Open
Drive Pre Running
Drive Run Commanded
Restart Delay Active
Drive Running
Drive Stopping
Running in Bypass
Entering Energy Savings
Energy Savings Active
Exiting Energy Savings
Auto Transfer Active
Remote Transfer Active
Emergency Override Drive FWD
Emergency Override Drive REV
Emergency Override Bypass
Faulted
Soft Start On Delay
Soft Starter Ramping down
YASKAWA TOEPYAIH6B01A HV600 AC Drive Narrow Bypass Installation & Startup
Shown on initial power up of the bypass system. This message goes away when the power up initialization is complete and
communication is established to the drive, or when the bypass determines that the drive is not connected or energized.
The bypass is in an Idle state with no active Run command. There are no active faults or alarms.
The drive is not in a ready state. The drive will not run if a Run command is asserted. You can run the system in Bypass
Mode.
A safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
A Fire Stat safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
A Freeze Stat safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
A Smoke Alarm safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
An Over Pressure safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
A Low Suction safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
A Vibration safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
Programmed BAS Interlock is not closed. The unit will not run when it receives a Run command.
The drive received a Run command and the drive is entering the programmed pre-run. When the pre-run conditions are
finished, the drive will enter drive run.
The bypass has commanded the drive to run, but it has not yet detected t that the drive is running.
There is an active Run Command, but the programmed restart delay is active and the drive cannot run. The keypad shows this
display on power-up or when there is a brief power loss to the bypass unit.
The unit is running in Drive Mode.
The Run command to the drive was removed, and the drive is ramping to stop.
The unit is running in Bypass Mode.
Energy savings conditions have been detected. This functionality is programmed using parameters Z1-16 through Z1-23.
When entering energy savings, the unit is running at the energy savings bump frequency and when it is finished, it will
switch into the bypass run state.
Energy Savings Mode is active and the unit is running in Bypass Mode.
Energy Savings conditions are no longer present and the unit is leaving Energy Savings and returning to Drive Mode. The
exit conditions are when the frequency reference changes from the programmed Energy Savings frequency reference in Z1-
17.
Auto transfer was enabled in Z1-05 and the unit detected a drive fault during an active drive run. The unit will run in Bypass
Mode.
A Remote Transfer was asserted and the unit is currently running in Bypass Mode.
An Emergency Override Drive FWD was asserted by a bypass digital input or through serial or option board communications
to the bypass board.
An Emergency Override Drive REV was asserted by a bypass digital input or through serial or option board communications
to the bypass board.
An Emergency Override Bypass was asserted by a bypass digital input or through serial or option board communications to
the bypass board. This message also appears when Emergency Override Drive was active, there was a drive fault, and Z1-10
= 1 [Transfer to Bypass].
The unit is in Drive Mode it detected a drive fault or bypass fault, or the unit is in Bypass Mode and it detected a bypass-
specific fault.
There is a Run command and the unit is waiting for the programmed on delay time in Z1-43 before asserting the soft starter
run.
Parameter Z1-42 = 2 [Ramp to Stop] and the Run command was removed. The soft starter will ramp to stop.

5.10 Bypass Status Messages

Description
5