Chapter 5: Wiring the SBxPWRSYS1-80 DC Power Supply
Connecting the Grounding Wire with Bare Wire
128
To attach the grounding wire to the power supply with bare wire, perform
the following procedure:
1. Prepare an adequate length of solid or stranded 10 AWG grounding
wire by stripping it as shown in Figure 75.
Figure 75. Stripping the solid or Stranded Grounding Wire
2. Verify that the On/Off switch on SBxPWRSYS1-80 DC Power Supply
is in the Off position. Refer to Figure 71 on page 124.
3. Use an 8 mm wrench to remove the grounding post nut and washer,
shown in Figure 72 on page 125, from the grounding post on the
power supply.
4. Wrap the grounding wire clockwise around the base of the grounding
post, as shown in Figure 76 on page 129.