Connecting The Grounding Wire; Figure 30: Stripping The Grounding Wire - Allied Telesis AT-IE300-12GP Installation Manual

Ie300 series. industrial ethernet switches
Hide thumbs Also See for AT-IE300-12GP:
Table of Contents

Advertisement

Chapter 5: Powering On the Switch

Connecting the Grounding Wire

84
Here are the guidelines for the grounding wire:
The wire should be minimum #16 AWG solid wire.
The wire length should be as short as possible.
Continuity from the grounding screw to the earth ground must be
less than 0.05 ohms.
If a terminal is used, it should be double crimped.
Warning
This equipment must be earthed. The ground screw on the unit must
be connected to a properly earthed bonding point.
To connect the grounding wire with bare wire, perform the following
procedure:
1. Strip 2.54cm (1.0 in.) of insulation from the end of the solid grounding
wire with a wire insulator stripper. Refer to Figure 30.
Figure 30. Stripping the Grounding Wire
Warning
Do not strip more than the recommended amount of wire. Stripping
more than the recommended amount can create a safety hazard by
leaving exposed wire on the terminal block after installation.  E10
2. Loosen the grounding screw several turns with a #2 Phillips-head
screwdriver. Refer to Figure 31 on page 85.
2.54cm
(1.0 in.)