Nortel DMS-100 Series Maintenance Manual page 310

Subscriber carrier module-100s
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

7-104 Card replacement procedures
NT6X92
SMS
(continued)
At the frame
10
11
297-8231-550 Standard 09.01 August 1998
WARNING
Static electricity damage
Before removing any cards, put on a wrist strap and
connect it to the wrist strap grounding point at the left
side of the frame supervisory panel of the SMS. This
protects the equipment against damage caused by
static electricity.
Put on a wrist strap.
WARNING
Equipment damage
When removing or inserting a card, do not apply
direct pressure to the components and do not force the
cards into the slots.
Remove the NT6X92 card from slot 17 as shown in the following figures.
a.
Locate the card to be removed on the appropriate shelf.
b.
Open the locking levers on the card to be replaced and gently pull the card
toward you until it clears the shelf.
c.
Verify the replacement card has the same PEC, including suffix, as the card
you just removed.