Nortel DMS-100 Series Maintenance Manual page 180

Subscriber carrier module-100s
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

6-16 Alarm clearing procedures
PM SMS
major
(continued)
31
32
33
297-8231-550 Standard 09.01 August 1998
To display information about the P-side links, type
>TRNSL P
and press the Enter key.
Example of a MAP response:
LINK 1 xxx xxx0 01 0 1;CAP S;STATUS: SysB
LINK 2 xxx xxx0 01 0 2;CAP S;STATUS: OK
LINK 3 xxx xxx0 01 0 3;CAP MS;STATUS: OK MSGCOND: OPN
LINK 4 xxx xxx0 01 0 4;CAP MS;STATUS: OK MSGCOND: OPN
LINK 5 xxx xxx0 01 0 5;CAP S;STATUS: OK
To busy the SysB link, type
>BSY LINK link_no
and press the Enter key.
where
link_no
is the number of the SysB link displayed in step 31
To test the link from step 32, type
>TST LINK link_no
and press the Enter key.
where
link_no
is the number of the link busied in step 32
If test
passes
fails
Do
step 36
step 34