Nortel DMS-100 Series Maintenance Manual page 144

Subscriber carrier module-100s
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

4-8 Converting from Mode I to Mode II
8 Post and busy the SMS at the PM level and perform a warm SWACT.
297-8231-550 Standard 09.01 August 1998
>POS SMS 0
>CHA
MACHINES NOT IN SYNC – DMOS NOT ALLOWED
JOURNAL FILE UNAVAILABLE – DMOS NOT ALLOWED
ENTER Y TO CONTINUE PROCESSING OR N TO QUIT
>Y
Step through the fields until the port to change appears. Press the Enter
key to step through the fields.
PSLNKTAB: 0 DS1 DEFAULT N
> 0 NILTYPE
PSLNKTAB: 2 DS1 DEFAULT N
> 2 NILTYPE
PSLNKTAB: 10 DS1 DEFAULT N
> 10 NILTYPE
PSLNKTAB: 12 DS1 DEFAULT N
> 12 NILTYPE
Step through the fields that remain until the tuple to change appears.
Press the Enter key to step through the fields that remain.
ENTER Y TO CONFIRM, N TO REJECT OR E TO EDIT.
>Y
TUPLE CHANGED
JOURNAL FILE INACTIVE
>QUIT
>MAPCI;MTC;PM
>POST SMS sms no
>BSY UNIT inactive unit no
>RTS UNIT inactive unit no
>SWACT
Example:
>MAPCI;MTC;PM