Nortel DMS-100 Series Maintenance Manual page 202

Subscriber carrier module-100s
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

6-38
6-38
Alarm clearing common procedures
Updating static data
XPM
Application
Use this procedure to update static data in the XPM.
Action
This procedure contains a summary flowchart and a list of steps. Use the
flowchart to review the procedure. Follow the steps to perform the
procedure.
297-8231-550 Standard 09.01 August 1998
6-38
The following RTS procedure(s) with the NODATASYNC option only
apply to XPMs not converted to XPM configuration data table (CDT)
management.
The XPMs with software loads that contain this feature synchronize
the node and port tables of both units with the CM.
These XPMs do not synchronize unit to unit.
All the XPM must be BSYed and RTSed to clear an ISTb condition
with configuration download and to synchronize both units.
This process must occur during periods of low traffic only to minimize
out-of-service impact.