7-94 Card replacement procedures
NT6X86
SMS
(continued)
4
5
6
297-8231-550 Standard 09.01 August 1998
By observing the MAP display, be sure the card to be removed is on the
inactive unit.
If faulty card is on
active unit
inactive unit
Switch the activity of the units by typing
>SWACT
and pressing the Enter key.
The system determines the type of SWACT it can perform and displays a
confirmation prompt for the selected SWACT.
If SWACT
can continue at this time
cannot continue at this time
Switch the activity of the unit by typing
>YES
and pressing the Enter key.
The system runs a pre-SWACT audit to determine the ability of the inactive unit
to accept activity reliably.
Note: A maintenance flag appears when maintenance tasks are in progress.
Wait until the flag disappears before proceeding with the next maintenance
action.
If the message is
SwAct passed
SwAct failed
SwAct failed
Reason: XPM SwActback
SwAct refused by SwAct
controller
Do
step 5
step 8
Do
step 6
step 23
Do
step 8
step 7
step 7
step 7