Reset Password & IP Address
If you lose the password or IP Address to the DMS-3K WEB Browser, first try the original defaults supplied with the
equipment:
IP Address: 192.168.250.100
User Name:
admin
Passwword:
admin
If that doesn't work, you can follow the procedure below for viewing and resetting the IP Address and Passwords.
Procedure to Reset IP Address and Passwords
1.
Remove power from the system.
2.
Remove any plates and modules from the two card slots near the CPU.
3.
Press and hold the switch SW10 shown above and power up the unit. Release the switch after power up.
4.
Power down the system.
5.
Connect a standard modem (1-1, straight thru) cable to the CPU DB9 serial port and the other to your PC.
6.
Power up system and wait at least 15 seconds.
7.
Connect to the unit using a PC Terminal application (like hyper terminal) using: 9600 baud, 8 bit, no parity and 1 stop.