Ametek DMS-3K Installation & Operation Manual page 83

Distributed monitoring system
Table of Contents

Advertisement

Control Inputs Configuration
Notes:
I/R Card installed in slot #10. Card Dip
Switches set to start input numbering
at 129
Test Pushbutton configured for Group
1 (controls all inputs). Wired to input
terminal 129 (I/R module input 1)
One Acknowledge PB configured for
Group 2 (inputs 1-8) Wired to input
terminal 130 (I/R module input 2)
One Acknowledge PB configured for
Group 3 (inputs 9-16) Wired to input
terminal 131 (I/R module input 3)
One Reset PB configured for Group 3
(inputs 9-16) Wired to input terminal
132 (I/R module input 4)
Sequence A configured for group 2
(inputs 1-8)
Sequence M configured for group 3
(inputs 9-16)
Page 71 of 206