I/O Modules - Ametek DMS-3K Installation & Operation Manual

Distributed monitoring system
Table of Contents

Advertisement

I/O Modules

The DMS-3K System can support a variety of I/O Modules:
8 I/O 8 digital inputs and 8 solid state outputs
16 I
16 digital inputs
16O
16 solid state outputs
8RR 8 relay contact outputs
16RR 16 relay contact outputs
5PR 5 relay contact outputs
8PR 8 relay contact outputs
I/R
4 digital inputs and 6 relay contact outputs
8 IAM 8 analog inputs (4-20mA)
8 I/O Module
This module accepts 8 digital contact inputs and provides 8 digital solid state outputs. The
digital inputs can use field contact voltages of 24, 48 or 125VDC. The field contact voltage can
be provided internally via the power supply regulator or externally supplied by the customer.
Digital Inputs can be Field Contacts, Control Pushbuttons (Ack, Test, Reset, etc), as assigned
via the web browser. Digital Outputs can be configured as Lamp Outputs (for remote
Annunciator display) or Horn Outputs (for direct connection to low power audible devices or to
the Regulator Module Horn Input to drive external high power devices).
The variations available are:
8 I/O Module
8 I/O 90
8 I/O 91
8 I/O 92
8 I/O 95
The Modules may have a suffix of A or B depending on the version. Ex. 8I/O 90B
10
Inputs
24 VDC FCV, Internally
24 VDC FCV, Externally
48 VDC FCV, Externally
125VDC FCV, Externally