Ametek DMS-3K Installation & Operation Manual page 199

Distributed monitoring system
Table of Contents

Advertisement

Unit
Diagnostic Events
Internal Communication Events
M/S
Cold Start with Default Settings
M/S
Received invalid Event code(X) for input
number(Y)
M/S
Communications Failure with Main Board
M/S
Communications Restored with Main Board
Unit
Time Sync Events
M/S
Hourly Time Update
M/S
Obtained IRIG-B Synchronization
M/S
Lost IRIG-B Synchronization
M/S
Obtained IRIG-B Synchronization
M/S
Lost IRIG-B Synchronization
S
Obtained Serial Synchronization
S
Lost Serial Synchronization
Page 187
(Descriptor 'D')
(Descriptor 'T')
Description
This should only occur if the main board is jumpered to
reinitialize the Alarm Input/Output configuration
Main Board firmware is out of date with Web board
firmware; (Should Not occur)
This event may occur immediately after a firmware
upgrade. It is usually pared with the event
"Communications Restored with main Board". If you do not
see the Restored event then a hardware failure has
occurred.
When an internal communications failure occurred but has
been corrected you will see this events. Should only occur
after a firmware upgrade.
Description
Time updated on the hour successfully between the Main
Board and WEB Board
IRIG-B Time Sync signal detected
The IRIG-B Time Sync signal was lost
IRIG-B Time Sync signal detected
The IRIG-B Time Sync signal was lost
Slave unit has synchronized it's time to the master via the
RS485 time sync
Slave unit has lost it's synchronization to the master via the
RS485 time sync