Control Inputs Configuration
The Control Inputs Configuration page is used for setting up which control pushbuttons are
used and what terminals they are connected to. This page is also used for setting up the
different operating sequences which determines how the lamp outputs, Horn Outputs and
Control Pushbuttons (Test, Ack, Reset, etc) function. Up to 64 Control Inputs are available.
Control Input pushbuttons and switches are connected to the 8 I/O, 16 I or I/R modules.
Figure 3–13. Control Inputs Configuration Page
Input Terminal:
The Input Terminal assignment is based on the number of digital Alarm Inputs in the system
and the switch settings used for that module. These Input terminals should start after the last
input number configured up to a maximum of Input Terminal 192. Example: In a system
60