Email Configuration

The DMS-3K can transmit any alarm to three separate email recipients. All alarms or specific ones
can be used to trigger an email. The alarm email will include the input number, time and date of alarm
and the alarm legend configured in the unit. The frequency of emails can be configured to send them
out as soon as an alarm occurs or batch them up at specified intervals.
The SMTP Server IP address or host name needs to be entered based on whatever email system
you are using. You must include your username and password that is used for this system. Consult
your IT administrator if unsure of the settings. After configuring the SMTP selections, you can test the
settings by pressing the 'Test SMTP Server Connection'. If the SMTP Server address is not
recognized, it will provide an error message when you try to save the Email settings.
Enter the recipient email address and select which alarms will trigger the email notification. The
frequency of how often the emails will be sent can be configured as '0' which is immediately after an
alarm or in hourly increments from 1 to 24. When a selection of 1-24 is used, any alarms that
occurred in that interval will be included in the email. Selecting 'Active Alarms' will only provide alarm
inputs that are in the alarm state at the time the email is generated. Selecting 'All Events' will include
Active Alarms and Alarms that returned to Normal.
Figure 3–25 Email Configuration Page
88