DMS-3K SPECIFICATIONS

Specifications are subject to change without notice.

System Capacity

16 I/O Card Racks per system
• 2,048 digital inputs or 512 analogs or combination of both
• 3,584 outputs per remote unit
• 640,000 events in non-volatile memory

I/O Card Rack Capacity

• 128 digital inputs or 32 analogs or combination of both
• 240 outputs per remote unit
• 40,000 events in non-volatile memory

INPUTS

Digital Inputs (8 I/O, 16I, I/R)
• N.O. or N.C., field contact selectable via browser config or DIP switches
Input Current
• Approximately 2mA per input
Input Loop Resistance
• N.O. Field Contacts:
• N.C. Field Contacts:
Field Contact Voltage
Internally Supplied Field Contact Voltage:
Externally Supplied Field Contact Voltage: 24 VDC, 48 VDC, 125VDC +/- 12.5%
Input Response
• Hardware Filter:
• Software Filter:
200K ohm minimum
1K ohm maximum
16 msec
(Timestamp corrected to show Alarm within 1 msec of occurrence)
Adjustable filter from 1-65,536 msec
24 VDC nominal
Page 157