REGULATOR Type REG-96 and REG-97
This unit is used in 3U logic boxes where the system supply is 48V DC.
It provides the 5V supply necessary for the 10 usable slots plus the CPU, which equates to 128
inputs and 160 outputs maximum.
An auxiliary horn relay is mounted within.
REG-96 (STANDARD) Intended for use where the initiating contacts are being powered from
the 48 V supply voltage.
REG-97 (ISOLATED) Intended for use where the initiating contacts are being powered from a
supply other than the system supply. This isolated supply would be connected to "+VIN" and
"OV IN" terminals.
All connections to the above units are by screw type terminals.
REGULATOR Type REG-94 and REG-95
This unit is used in 6U logic boxes where the system supply is 48V DC.
It provides the 5V supply necessary for the 23 usable slots plus the CPU which equates to 128
inputs and 240 outputs including auxiliary cards to box capacity. Otherwise they are generally
as per REG-96/97.
REG-94 - (STANDARD)
REG-95 - (ISOLATED)
CPU-200
The CPU is used to configure the system and provide serial and Ethernet outputs for real time alarm
status. The CPU has a 9 pin D connector for serial communications, RJ45 port for Ethernet
communications, BNC connector for IRG-B time synchronization and a LED for system status. The
serial port is used for real time alarm outputs using Modbus, DNP or ASCII outputs depending on the
application. The Ethernet port is used for configuring the unit using any standard web browser. The
Ethernet port is also used for real time alarm outputs using Modbus TCP/IP and DNP outputs. The
Ethernet Port can be used for external time synchronization using NTP time formats.