Reg-92 (Reg-93) Module Specifications
SYSTEM SUPPLY
Nominal Supply Voltage:
Minimum Supply Voltage:
Maximum Supply Voltage:
The System supply voltage can be unregulated and used for Lamp Voltage and audible Supply. The '+V' supply
is internally regulated with limited current load rating. It is required to supply the small current load requirement of
the alarm initiating contacts and control switches to ensure the input response parameters are kept within the
specified limits.
OUTPUT 1
Contact wetting supply:
OUTPUT 2 (Internal)
Logic supply:
Relay
Audible (or Auxiliary) relay
COMPATIBITY TABLE
The DMS-3K module range is fully backwards compatible with previous versions of this product, namely:
MPAS90
(Highland Electronics Limited)
RTU3000
Rochester Instrument systems Limited
DMS3000
AMETEK Power Instruments Limited
The REGULATOR modules are backward compatible per the following table
DMS-3K MODULE
Module Ref
Part No*
REG-92B
1087-409
REG-93B
1087-411
(*Assembly Part Numbers listed include Front Panel and Wiring Connectors)
REG-94 (REG-95)
This unit is used in 6U logic boxes where the system supply is 48V DC.
24V DC
21V DC
27V DC
24V DC ± 1v @ 1 Amp Maximum
5V DC ± 0.25v @ 5.0 Amp Maximum
Short Circuit Protected
The 5V Supply is not available as an output
DO NOT attempt to use this supply for external use.
24V Coil
Rating 2 Amp @240V a.c. Max
Form A (Normally Open) Contact
COMPATIBLE MODULES
Module Ref
Part No
REG-92A
8025-215
REG-93A
8025-229
Comment
Two part Edge Connector
Two part Edge Connector