8 IAM Module
This module can accept 8 Analog Inputs (4-20mA). The inputs require an external 24VDC
power supply for use in 2 wire systems. Each analog input is configured for up to 4 trip points
which can be used to drive lamp outputs, alarm relays and horns. Connection is by screw type
terminals (1.5mm², 16 AWG max.).

Annunciator Displays

The DMS-3K System can be connected to a remote Annunciator Display(s) using several methods:
-Solid State Lamp Outputs
In this configuration, the DMS would provide solid state outputs (8 I/O or 16O modules) that
would be cabled to a remote Annunciator Display. The lamp outputs would be configured to
follow a operating sequence and respond to pushbutton controls. Outputs can be directly wired
to the display in multi-conductor cables. The cables are either connected directly to the output
module terminal blocks or with a plug-in connector arrangement.
The following Annunciator Displays are compatible with the DMS-3K Lamp Outputs:
• AN-3100D-LC / Series 90A-LC
• AN-6150
• AN-5131
This display can be configured in cell configurations up to 13 rows high by 13
columns wide (max 169 cells) and each cell has 4 window sizes available: Quad
1.5H x 1.5W", Triple 1.0H x 3.0W", Dual 1.5H x 3.0W", Single 3.0H x 3.0W".
Customer connections can be made using a plug-in connector or directly to
'barrier' style terminal blocks. The display comes with LED lamps as standard.
This display can be configured in cell configurations up to 6 rows high by 6
columns wide (max 36 cells) and each cell has 4 window sizes available: Small
0.98H x 1.14W", Medium 0.98W x 2.40H", Large 2.13H x 2.40W", Extra large
2.13H x 4.96W". It can support a maximum of 288 windows. Customer
connections can be made using a plug-in connector or directly to 'barrier' style
terminal blocks. The display comes with incandescent bulbs as standard and can
be upgraded with LED replacements.
This display can be configured in cell configurations up to 10 rows high by 10
columns wide (max 100 cells) and each cell has 4 window sizes available: Quad
0.38H x 2.85W", Triple 1.11H x 2.85W", Dual 1.67H x 2.85W", Single 3.34H x
2.85W". Customer connections can be made using a plug-in connector or directly
to 'barrier' style terminal blocks. The display comes with incandescent bulbs as
standard and can be upgraded with LED replacements.